Cable Connection - ABB SafeRing Installation And Operating Instructions Manual

Sf6 insulated ring main unit and compact switchgear
Table of Contents

Advertisement

SafeRing / SafePlus
SF 6 insulated ring main unit and compact switchgear
Installation and operating instructions
Adjustable cable support beam (additional equipment).
Cable support beam
Cable clamp
ABB / PTMV
Earthing bar

4.2 CABLE CONNECTION

SafeRing/ SafePlus is equipped with external bushings which
comply with DIN47636T1 & T2/EDF HN 525-61 for termination of
cables.
All bushings are situated in the same height from the floor and are
protected by the cable cover.
SafeRing / SafePlus can be supplied with the following bushings
for the various type of cubicle.
Type of
module
C
Bushings
200 series plug in
X
400 series plug in
X
400 series bolted
X
600 series bolted
Cable adapters
The following types are recommended:
ABB Kabeldon
ABB Kabel und Draht
Elastimold
Raychem
Cooper
3M
Please see supplier documentation for details.
The manufacturer's installation instructions must be followed. Be
sure to lubricate the bushings thoroughly with the silicone supplied.
NB!
Where cables are not connected, the earthing switch must be
locked in closed position or the bushings must be fitted with
deadend recepticals before the unit is put into operation.
F
V
X
X
X
X
X
X
400 S Bolt
600 S Bolt
400 S Plug
200 S Plug
NHP 408033
11
NOPOWSR 5976 GB