Fuse Table For Modules - ABB SafeRing Installation And Operating Instructions Manual

Sf6 insulated ring main unit and compact switchgear
Table of Contents

Advertisement

SafeRing / SafePlus
SF 6 insulated ring main unit and compact switchgear
Installation and operating instructions

3.2 FUSE TABLE FOR MODULES

100%
UN (kV)
25
50
3
16
25
3,3
16
25
4,15
10
16
5
10
16
5,5
6
16
6
6
16
6,6
6
16
10
6
10
11
6
6
12
6
6
13,8
6
6
15
6
6
17,5
6
6
20
6
6
22
6
6
24
6
6
– The table is based on using fuses type ABB CEF
– Normal operating conditions with no overload
– Ambient temperature -25°C + 40°C
120%
UN (kV)
25
50
3
16
25
3,3
16
25
4,15
10
16
5
10
16
5,5
6
16
6
6
16
6,6
6
16
10
6
10
11
6
6
12
6
6
13,8
6
6
15
6
6
17,5
6
6
20
6
6
22
6
6
24
6
6
– The table is based on using fuses type ABB CEF
– Normal operating conditions with 20% overload
– Ambient temperature -25°C + 40°C
8
NOPOWSR 5976 GB
75
100
125
160
200
25
40
40
50
25
40
40
50
25
25
40
40
25
25
25
40
16
25
Ny tabell kommer
25
25
16
25
25
25
16
25
25
25
10
16
16
25
10
16
16
25
10
16
16
16
10
10
16
16
10
10
16
16
6
10
10
16
6
10
10
16
6
6
10
10
6
6
10
10
75
100
125
160
200
25
40
40
50
25
40
40
50
25
25
40
40
25
25
25
40
16
25
25
25
16
25
25
25
16
25
25
25
10
16
16
25
10
16
16
25
10
16
16
16
10
10
16
16
10
10
16
16
6
10
10
16
6
10
10
16
6
6
10
10
6
6
10
10
Transformer rating (kVA):
250
315
400
50
80
100
125
50
63
80
100
50
50
63
80
40
50
50
63
40
50
50
63
40
40
50
50
40
40
50
50
25
25
40
40
25
25
25
40
25
25
25
40
25
25
25
25
16
25
25
25
16
16
25
25
16
16
25
25
16
16
16
25
16
16
16
25
Transformer rating (kVA):
250
315
400
63
80
100
125
63
80
80
100
50
63
80
80
40
50
63
80
40
50
50
80
40
40
50
63
40
40
50
63
25
25
40
40
25
25
25
40
25
25
25
40
25
25
25
25
16
25
25
25
16
16
25
25
16
16
25
25
16
16
16
25
16
16
16
25
500
630
800
1000
160
160
125
160
100
125
160
80
100
160
160
80
100
125
160
80
100
125
160
63
80
100
125
50
50
80
80
50
50
63
80
40
50
63
80
40
50
50
63
40
40
50
63
25
40
50
50
25
40
40
50
25
25
40
50
25
25
40
40
500
630
800
1000
160
125
100
125
80
125
160
80
100
125
160
80
100
125
160
80
80
100
125
50
63
80
80
50
50
80
80
40
50
63
80
40
50
50
80
40
40
50
63
25
40
50
50
25
40
40
50
25
25
40
50
25
25
40
40
CEF
1250 1600
160
160
125
125
100
125
100
125
80
100
80
100
63
80
63
63
50
63
50
63
CEF
1250 1600
125
100
125
100
125
80
100
80
100
63
80
63
50
63
50
63
ABB / PTMV