Fan coil/systemised building technology
Hide thumbs Also See for i-bus KNX:

Advertisement

Designation
Proportional range of the
cooling controller
Integration time of the
cooling controller
Values
1 K, 1.5 K, 2 K, 2.5 K, 3 K
3.5 K, 4 K, 4.5 K
5 K, 5.5 K, 6 K
6.5 K, 7 K, 7.5 K
8 K, 8.5 K
15 mins., 30 mins., 45
mins.,
60 mins., 75 mins., 90
mins.,
105 mins.,, 120 mins., 135
mins., 150 mins., 165
mins., 180 mins., 195
mins., 210 mins., 225 mins.
Meaning
Professional setting for
modifying the controller
behaviour for the room.
Large values result in less
dramatic changes in the
control values when the
control deviation remains
the same, and gives more
precise control than lower
values.
The integration time
determines the response
time of the control.
It specifies the increase by
which the output control
value is increased in
addition to the P-
component. The I-
component remains active
for as long as there is a
control deviation. The I-
component is increased by
the P-component.
See in appendix:
B ehaviour of the PI
H U
controller
U H