Instantaneous Derived Earth Fault Protection (50N); Figure 3-3 Logic Diagram: Derived Instantaneous Earth Fault Element - Siemens 7SR45 Argus User Manual

Self powered overcurrent and earth fault relay
Hide thumbs Also See for 7SR45 Argus:
Table of Contents

Advertisement

The following are the 51-n supported Curve Characteristic:
· DTL, IEC-NI, IEC-VI, IEC-EI, IEC-LTI, ANSI-MI, ANSI-VI, ANSI-EI
Table 3-2
Parameters
Description
51-n Element
51-1 Block
51-n Setting
Current Set point
51-n Char
Characteristics
51-n Time
Time Multiplier
Mult
(other than DTL)
Delay
51-n Delay
(Applicable only for
DTL)
51-n Min
Minimum Operate
Operate
Time
51-n Follower
Follower DTL
51-n Reset
Reset
3.3

Instantaneous Derived Earth Fault Protection (50N)

Earth current is derived by calculating the sum of the measured line currents.
Two instantaneous derived earth fault elements are provided in the 7SR45 self powered overcurrent and earth
fault relay.
50N-1, 50N-2
Each instantaneous element has independent settings for pick-up current 50N-n Setting and a definite time delay
50N-n Delay.
Operation of the instantaneous derived earth fault elements can be inhibited from:
Inhibit 50N-n
Figure 3-3
© 2017 Siemens Protection Devices Limited
Time Delayed Overcurrent Protection (51-n)
Default Value
Disabled
1xIn
DTL
1
5 s
0 s
0 s
0 s
A binary input.
Logic Diagram: Derived Instantaneous Earth Fault Element
7SR45 Description of Operation
Min
Max
Step Change
-
-
-
0.2xIn
2.0xIn
0.01
-
-
-
0.01 s
10
0.01
0 s
15 s
0.01
0 s
20 s
0.01
0 s
20 s
0.01
60, IEC/
0 s
ANSI
1
DECAY
Chapter 1 Page 18 of 34