ABB 615 Series ANSI Manual page 45

Modbus communication protocol
Hide thumbs Also See for 615 Series ANSI:
Table of Contents

Advertisement

1MAC052634-MB D
615/620 series ANSI
Communication Protocol Manual
Table 29:
Header part of the record structure
1
Register
Address
4xxxx
Fault record selection
4xxxx + 1
Sequence Number
4xxxx + 2
Unread records left
4xxxx + 3
TimeStamp (Year,Month)
4xxxx + 4
TimeStamp (Day, Hour)
4xxxx + 5
TimeStamp (Min, Sec)
4xxxx + 6
TimeStamp (Milliseconds)
4xxxx + 7
Time quality
4xxxx + 8
From this location onwards starts the Fault record application data.
1. See Modbus ANSI point list manual for specific event record structure mapping.
Fault record application data part
The data in the application section are IED type dependent. The description of the data is
found in the Modbus fault record section of the Modbus memory map.
Fault record reading
As long as there are unread fault records available for the Modbus client in question, bit 1
of the Modbus SSR3 register remains "1".
The fault record reading is done in two steps. First, the client writes a selection code to the
Fault record selection register. The selection code defines the type of read operation that
the client wants to do. The selected fault record is loaded by the IED into the following N
registers (4xxxx-NNNN). See Modbus ANSI point list manual for specific fault record
structure mapping. Second, the client reads out these registers in one multiple register read
operation.
The fault records can be read by using two commands, the function 5 for
the write operation and the function 6 for the read operation, or by using
the function 23 that includes write and read operations in the same
transaction.
If the fault records are read by using two commands, the positive
confirmation to the write select operation tells the client that a fault record
has been loaded for reading. Another way to detect the positive
confirmation is by monitoring the state of SSR3 bit 9.
Fault record structure length
Since the application data part is IED type dependent, the length of the fault record
structures vary in different types of IEDs. A client can read out more Modbus registers
than are actually coded in one structure when reading out the data structures. The
maximum read amount is 80 Modbus registers. The additional trailing registers contain the
Vendor-specific implementation
Values
Comment
1...4 and -1...-99
Write register
0...65535
0...99
High byte:year, low byte:month
High byte:day, low byte:hour
High byte:min, low byte:second
Word: milliseconds (0...999)
Section 3
39

Advertisement

Table of Contents
loading

This manual is also suitable for:

620 series ansiRelion 615 series

Table of Contents