CHAPTER 2: RS485 INTERFACE
SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
INF
Semantics
<72>
Trip I>> (back-up operation)
<73>
Fault location X in ohms
<74>
Fault forward / line
<75>
Fault reverse / busbar
<76>
Teleprotection signal transmitted
<77>
Teleprotection signal received
<78>
Zone 1
<79>
Zone 2
<80>
Zone 3
<81>
Zone 4
<82>
Zone 5
<83>
Zone 6
<84>
General start / pick-up
<85>
Breaker failure
<86>
Trip measuring system L1
<87>
Trip measuring system L2
<88>
Trip measuring system L3
<89>
Trip measuring system E
<90>
Trip I>
<91>
Trip I>>
<92>
Trip IN>
<93>
Trip IN>>
Table 2-9: Auto-reclosure indications in monitor direction
INF
Semantics
<128>
CB 'on' by AR
<129>
CB 'on' by long-time AR
<130>
AR blocked
Table 2-10: Measurands in monitor direction
INF
Semantics
<144>
Measurand I
<145>
Measurands I, V
<146>
Measurands I, V, P, Q
<147>
Measurands In, Ven
<148>
Measurands IL123, VL123, P, Q, f
Table 2-11: Generic functions in monitor direction
INF
<240>
<241>
<243>
<244>
<245>
IEC 60870-5-103 SERIAL COMMUNICATION
3 Series relay
Identifier
3 Series relay
Identifier
3 Series relay
Identifier
Semantics
Read headings of all defined groups
Read values or attributes of all entries of one group
Read directory of a single entry
Read value or attribute of a single entry
End of general interrogation of generic data
3 Series relay
Data Text
3 Series relay
Data Text
3 Series relay
Data Text
2-19