CHAPTER 4: 3 SERIES IEC61850 GOOSE

GOOSE Rx status

Data Item
eDataRemoteGOOSEStatus
eDataRemoteGOOSEHeaderStatus Remote GOOSE Header
SR3 SERIES PROTECTIVE RELAY PLATFORM – COMMUNICATIONS GUIDE
In order to visualize the status of the incoming GOOSE messages, the following status
registers are available in the MODBUS memory map:
EnerVista 3 Series
MMI Text
Setup Text
Remote GOOSE Status
REM GOOSE STAT 0xFFFF FFFF FC215
REM GOOSE HDR
Status
STAT
GOOSE 1
GOOSE 2
GOOSE 3
GOOSE 4
GOOSE 5
GOOSE 6
GOOSE 7
GOOSE 8
unsigned 32 bits
Enum
FC215
0x0001
0x0002
0x0004
0x0008
0x0010
0x0020
0x0040
0x0080
The GOOSE Header Status is set at 1 if all the header's filters are passed. Otherwise, the
Header Status will be set at 0.
After a GOOSE header is accepted, the 3 Series relay firmware either accepts or rejects the
associated dataset. The firmware bases this decision on the R
configured for the header. If both (Header and Dataset structure) are accepted, the Remote
GOOSE Status is set to 1, otherwise it is set to 0. If the header status is never set to 1, then
the associated GOOSE status always remains at 0.
The incoming GOOSE defines the timeout for the next message. GOOSE Header Status is
set to 0 if the next message is not received within the specified amount of time. GOOSE
Status is also set to 0 if the next message is not accepted within the specified amount of
time.
If a GOOSE message is received, and its header has not been configured for reception, the
firmware ignores the message.
It is possible to see this GOOSE status information from the 3 Series relay front panel.
Figure 4-3: EnerVista 3 Series Setup GOOSE Status page
GOOSE CONFIGURATION VIA THE 3 SERIES MENUS
Value
Format
Size in
Code
words
2
0xFFFF FFFF FC215
2
0x0000 0001
0x0000 0010
0x0000 0100
0x0000 1000
0x0001 0000
0x0010 0000
0x0100 0000
0x1000 0000
GOOSE Receive Status
eFMT_GOOSE1
eFMT_GOOSE2
eFMT_GOOSE3
eFMT_GOOSE4
eFMT_GOOSE5
eFMT_GOOSE6
eFMT_GOOSE7
eFMT_GOOSE8
dataset that has been
X
Modbus
Address
31515
31517
Text String
GOOSE 1 RECEIVED
GOOSE 2 RECEIVED
GOOSE 3 RECEIVED
GOOSE 4 RECEIVED
GOOSE 5 RECEIVED
GOOSE 6 RECEIVED
GOOSE 7 RECEIVED
GOOSE 8 RECEIVED