Summary of Contents for ABB RED670

  • Page 1 ® Relion 670 series Line differential protection RED670 2.1 IEC Product guide...
  • Page 2: Table Of Contents

    Disclaimer The information in this document is subject to change without notice and should not be construed as a commitment by ABB. ABB assumes no responsibility for any errors that may appear in this document. Drawings and diagrams are not binding.
  • Page 3: Application

    1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Issued: December 2015 Revision: - 1. Application The IED can be used in applications with IEC 61850-9-2LE The IED is used for the protection, control and monitoring of process bus with up to six merging units (MU) depending on overhead lines and cables in all types of networks.
  • Page 4 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 certificates and the distribution of such, a procedure completely • Single-breaker (double or single bus) with three phase transparent to the user. tripping (A31) • Single-breaker (double or single bus) with single phase...
  • Page 5 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Description of configuration A31 RED670 A31 – Single Breaker with Three phase tripping 12AI (6I+6U) WA2_VT VN MMXU WA1_VT VN MMXU 1→0 5(0→1) SC/VC SMP PTRC SMB RREC...
  • Page 6 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Description of configuration A32 RED670 A32 – Single Breaker with Single phase tripping 12AI (6I+6U) WA2_VT VN MMXU WA1_VT VN MMXU 1→0 5(0→1) SC/VC SMP PTRC SMB RREC...
  • Page 7 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Description of configuration B31 RED670 B31: interruptor múltiple con disparo trifásico 12AI (6I+6U) WA1_VT WA1_CT 50BF 3I>BF CC RBRF VN MMXU 50BF 3I>BF WA1_QA1 CC RBRF REM CT1...
  • Page 8 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Description of configuration B32 RED670 B32 – Multi Breaker with Single phase tripping 12AI (6I+6U) WA1_VT WA1_CT 50BF 3I>BF 52PD CC RBRF CC PDSC VN MMXU 50BF 3I>BF...
  • Page 9: Available Functions

    1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 2. Available functions Main protection functions Table 1. Example of quantities = number of basic instances = option quantities 3-A03 = optional function included in packages A03 (refer to ordering details)
  • Page 10 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 IEC 61850 ANSI Function description Line Differential RED670 (Customized) Differential protection HZPDIF 1Ph high impedance differential protection 3-A02 3-A02 3-A02 3-A02 REFPDIF Restricted earth fault protection, low impedance 0–2...
  • Page 11 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 IEC 61850 ANSI Function description Line Differential RED670 (Customized) PSPPPAM Pole slip/out-of-step protection 1-B22 1-B22 1-B22 1-B22 OOSPPAM Out-of-step protection 0–1 1-B22 1-B22 1-B22 1-B22 ZCVPSOF Automatic switch onto fault logic, voltage and current...
  • Page 12 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Back-up protection functions IEC 61850 ANSI Function description Line Differential RED670 (Customized) Current protection PHPIOC Instantaneous phase overcurrent protection OC4PTOC Four step phase overcurrent protection 51_67 EFPIOC...
  • Page 13 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 IEC 61850 ANSI Function description Line Differential RED670 (Customized) Multipurpose protection CVGAPC General current and voltage protection 4-F01 4-F01 4-F01 4-F01 General calculation SMAIHPAC Multipurpose filter 67 requires voltage...
  • Page 14 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Control and monitoring functions IEC 61850 ANSI Function description Line Differential RED670 Control SESRSYN Synchrocheck, energizing check and synchronizing SMBRREC Autorecloser 1-H04 2-H05 1-H04 2-H05 APC10 Apparatus control for single bay, max 10 apparatuses...
  • Page 15 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 IEC 61850 ANSI Function description Line Differential RED670 AND, GATE, INV, Basic configurable logic blocks (see Table 2) 40-280 40-28 40-280 40-28 40-28 LLD, OR, PULSETIMER, RSMEMORY,...
  • Page 16 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 IEC 61850 ANSI Function description Line Differential RED670 DRPRDRE, Disturbance report A1RADR- A4RADR, B1RBDR-B8RBDR SPGAPC Generic communication function for Single Point indication SP16GAPC Generic communication function for Single Point indication...
  • Page 17 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 2. Total number of instances for basic configurable logic blocks Basic configurable logic block Total number of instances GATE PULSETIMER RSMEMORY SRMEMORY TIMERSET Table 3. Total number of instances for configurable logic blocks Q/T...
  • Page 18 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Communication IEC 61850 ANSI Function description Line Differential RED670 (Customized) Station communication LONSPA, SPA SPA communication protocol LON communication protocol HORZCOMM Network variables via LON PROTOCOL Operation selection between SPA and IEC...
  • Page 19 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 IEC 61850 ANSI Function description Line Differential RED670 (Customized) OPTICAL103 IEC 60870-5-103 Optical serial communication RS485103 IEC 60870-5-103 serial communication for RS485 AGSAL Generic security application component...
  • Page 20 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Basic IED functions Table 5. Basic IED functions IEC 61850 or function Description name INTERRSIG SELFSUPEVLST Self supervision with internal event list TIMESYNCHGEN Time synchronization module BININPUT, SYNCHCAN,...
  • Page 21: Differential Protection

    1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 5. Basic IED functions, continued IEC 61850 or function Description name CAMCONFIG Central account management configuration CAMSTATUS Central account management status TOOLINF Tools Information component SAFEFILECOPY Safe file copy function Table 6.
  • Page 22 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Line differential protection, 3 or 6 CT sets L3CPDIF, L6CPDIF YNdx Line differential protection applies the Kirchhoff's law and compares the currents entering and leaving the protected...
  • Page 23 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 A line charging current compensation provides increased sensitivity of line differential protection. windings. Both two- and three-winding transformers are Line differential protection 3 or 6 CT sets, with in-zone...
  • Page 24: Impedance Protection

    1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Protected zone Comm. Channels en05000044.vsd IEC05000044 V1 EN Figure 10. Five terminal line with master-slave system Current samples from IEDs located geographically apart from The communication link is continuously monitored, and an...
  • Page 25 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Forward Forward operation operation Reverse Reverse operation operation en05000034.vsd en05000034.vsd IEC05000034 V1 EN IEC05000034 V1 EN Figure 11. Typical quadrilateral distance protection zone with Phase Figure 12.
  • Page 26 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 The extensive output signals from the phase selection gives mode (offset). This makes them suitable, together with different also important information about faulty phase(s), which can be communication schemes, for the protection of power lines and used for fault analysis.
  • Page 27 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 The distance protection zones can operate, independent of for load encroachment, which increases the possibility to each other, in directional (forward or reverse) or non-directional detect high resistive faults on heavily loaded lines, as shown in mode.
  • Page 28 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 achieve. Therefore, the function has a built in algorithm for load can even be decided separate for the phase-to-ground or encroachment, which gives the possibility to enlarge the phase-to-phase loops.
  • Page 29: Current Protection

    1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 other. If the connection between the generators is too weak the phase, when each group is equipped with current transformers. magnitude of the oscillations will increase until the angular The protection function performs a simple summation of the stability is lost.
  • Page 30 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 IDir, UPol and IPol can be independently selected to be either There is also available one nondirectional 3I0 step and one 3U0 zero sequence or negative sequence.
  • Page 31: Voltage Protection

    1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 The stub protection STBPTOC covers the zone between the 6. Voltage protection current transformers and the open disconnector. The three- Two step undervoltage protection UV2PTUV phase instantaneous overcurrent function is released from a...
  • Page 32: Frequency Protection

    1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Radial feeder protection PAPGAPC Overfrequency protection SAPTOF The PAPGAPC function is used to provide protection of radial Overfrequency protection function SAPTOF is applicable in all feeders having passive loads or weak end in-feed sources. It is...
  • Page 33: Secondary System Supervision

    1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 practice is more associated with voltage transformer switching Voltage-restrained time overcurrent protection VRPVOC during station operations. Voltage-restrained time overcurrent protection (VRPVOC) function can be used as generator backup protection against Fuse failure supervision VDSPVC short-circuits.
  • Page 34 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Autorecloser SMBRREC Interlocking The autorecloser SMBRREC function provides high-speed The interlocking function blocks the possibility to operate and/or delayed auto-reclosing for single or multi-breaker primary switching devices, for instance when a disconnector is applications.
  • Page 35: Scheme Communication

    1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 selection of the operator place per bay. QCBAY also provides same role as functions GOOSEBINRCV (for IEC 61850) and blocking functions that can be distributed to different MULTICMDRCV (for LON).
  • Page 36 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 In the directional scheme, information of the fault current Current reversal and weak-end infeed logic for distance direction must be transmitted to the other line end. With...
  • Page 37: Logic

    1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Following features are available: Zero sequence overcurrent protection LCZSPTOC Zero sequence components are present in all abnormal • Definite time stage for low active power protection conditions involving earth. They have a considerably high value •...
  • Page 38 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 • TIMERSET function has pick-up and drop-out delayed Group alarm logic function ALMCALH outputs related to the input signal. The timer has a settable The group alarm logic function ALMCALH is used to route time delay.
  • Page 39: Monitoring

    1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 • positive, negative and zero sequence currents and Boolean 16 to Integer conversion with logic node voltages representation BTIGAPC • mA, input currents Boolean 16 to integer conversion with logic node •...
  • Page 40 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Event list DRPRDRE Disturbance recorder DRPRDRE Continuous event-logging is useful for monitoring the system The Disturbance recorder function supplies fast, complete and from an overview perspective and is a complement to specific reliable information about disturbances in the power system.
  • Page 41: Metering

    1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 measure value expander block (RANGE_XP) has been setting values for limits. The output for each limit is activated introduced to enable translating the integer output signal from when the counted value reaches that limit.
  • Page 42: Human Machine Interface

    IEDs. The LHMI is used for setting, monitoring and controlling. SPA communication protocol A single glass or plastic port is provided for the ABB SPA protocol. This allows extensions of simple substation...
  • Page 43: Remote Communication

    1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 automation systems but the main use is for Substation Galvanic X.21 line data communication module X.21-LDCM Monitoring Systems SMS. A module with built-in galvanic X.21 converter which e.g. can be connected to modems for pilot wires is also available.
  • Page 44 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 bus) that use the IEC 61850-8-1 protocol (OEM rear port A, B). Electrical (BNC) and optical connection (ST) for 0XX and 12X The process bus use the IEC 61850-9-2LE protocol (OEM rear IRIG-B support.
  • Page 45 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 IEC06000182-2-en.vsd IEC06000182 V2 EN Figure 19. A 1/2 x 19” size IED side-by-side with RHGS6. xx08000165.vsd IEC08000165 V1 EN Figure 18. Case with rear cover and 19” rack mounting kit...
  • Page 46: Connection Diagrams

    1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 20. Connection diagrams Connection diagrams for Configured products Connection diagrams Connection diagram, RED670 2.1, A31 1MRK002803-HA The connection diagrams are delivered on the IED Connectivity Connection diagram, RED670 2.1, B31 1MRK002803-HB package DVD as part of the product delivery.
  • Page 47: Technical Data

    1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 21. Technical data General Definitions Reference value The specified value of an influencing factor to which are referred the characteristics of the equipment Nominal range The range of values of an influencing quantity (factor) within which, under specified conditions, the equipment meets the specified...
  • Page 48 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 9. MIM - mA input module Quantity: Rated value: Nominal range: Input resistance = 194 Ohm Input range ±5, ±10, ±20mA 0-5, 0-10, 0-20, 4-20mA Power consumption each mA-board £...
  • Page 49 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Binary inputs and outputs Table 12. BIM - Binary input module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ±20% 48/60 V RL ±20%...
  • Page 50 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 14. IOM - Binary input/output module Quantity Rated value Nominal range Binary inputs DC voltage, RL 24/30 V RL ±20% 48/60 V RL ±20% 110/125 V RL ±20%...
  • Page 51 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 16. IOM with MOV and IOM 220/250 V, 110mA - contact data (reference standard: IEC 61810-2) Function or quantity Trip and Signal relays Fast signal relays (parallel reed relay)
  • Page 52 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 18. SOM - Static Output module data (reference standard: IEC 61810-2): Electromechanical relay outputs Function of quantity Trip and signal relays Max system voltage 250V AC/DC...
  • Page 53 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 21. Auxiliary DC supply voltage influence on functionality during operation Dependence on Reference value Within nominal Influence range Ripple, in DC auxiliary voltage max. 2% 15% of EL 0.01% / %...
  • Page 54 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Type tests according to standards Table 23. Electromagnetic compatibility Test Type test values Reference standards 1 MHz burst disturbance 2.5 kV IEC 60255-26 100 kHz slow damped oscillatory wave immunity test 2.5 kV...
  • Page 55 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 25. Environmental tests Test Type test value Reference standard Cold operation test Test Ad for 16 h at -25°C IEC 60068-2-1 Cold storage test Test Ab for 16 h at -40°C...
  • Page 56 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Differential protection Table 28. Restricted earth-fault protection, low impedance REFPDIF Function Range or value Accuracy Operating characteristic Adaptable ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >95%...
  • Page 57 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 30. Line differential protection L3CPDIF,L6CPDIF,LT3CPDIF,LT6CPDIF Function Range or value Accuracy *Minimum operate current (20-200)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I > I SlopeSection2 (10.0-50.0)%...
  • Page 58 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 31. Additional security logic for differential protection LDRGFC Function Range or value Accuracy Operate current, zero sequence current (1-100)% of lBase ±1.0% of I Operate current, low current operation (1-100)% of lBase ±1.0% of I...
  • Page 59 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Impedance protection Table 32. Distance measuring zone, Quad ZMQPDIS Function Range or value Accuracy Number of zones Max 5 with selectable direction Minimum operate residual (5-1000)% of IBase...
  • Page 60 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 33. Distance measuring zone, quadrilateral characteristic for series compensated lines ZMCPDIS, ZMCAPDIS Function Range or value Accuracy Number of zones Max 5 with selectable direction IBase...
  • Page 61 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 35. Full-scheme distance protection, Mho characteristic ZMHPDIS Function Range or value Accuracy Number of zones, Ph-E Max 5 with selectable direction Minimum operate current (10–30)% of IBase Positive sequence impedance, ±2.0% static accuracy...
  • Page 62 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 37. Faulty phase identification with load encroachment FMPSPDIS Function Range or value Accuracy Load encroachment criteria: Load ±2.0% static accuracy (1.00–3000.00) W/phase resistance, forward and reverse (5–70) degrees...
  • Page 63 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 39. Phase selection with load encroachment, quadrilateral characteristic FRPSPDIS Function Range or value Accuracy Minimum operate current (5-500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I >...
  • Page 64 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 41. Distance zones quad with high speed distance for series compensated networks ZMFCPDIS Function Range or value Accuracy Number of zones 3 selectable directions, 3 fixed directions...
  • Page 65 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 43. Power swing logic PSLPSCH Function Range or value Accuracy Permitted maximum operating (0.000 — 60.0000) s ±0,2% or ±15 ms whichever is greater time difference between...
  • Page 66 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 46. Phase preference logic PPLPHIZ Function Range or value Accuracy Operate value, phase-to-phase (1 - 100)% of UBase ±0.5% of U and phase-to-neutral undervoltage Reset ratio, undervoltage <...
  • Page 67 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Current protection Table 48. Instantaneous phase overcurrent protection PHPIOC Function Range or value Accuracy Operate current (5-2500)% of lBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio >...
  • Page 68 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 49. Four-step phase overcurrent protection OC4PTOC Function Setting range Accuracy Operate current, step 1 - 4 (5-2500)% of lBase ±1.0% of I at I ≤ I ±1.0% of I at I >...
  • Page 69 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 51. Four step residual overcurrent protection EF4PTOC technical data Function Range or value Accuracy Operate current, step 1 - 4 (1-2500)% of lBase ±1.0% of I at I ≤...
  • Page 70 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 52. Four step negative sequence overcurrent protection NS4PTOC Function Range or value Accuracy Operate current, step 1 - 4 (1-2500)% of lBase ±1.0% of I at I £ I ±1.0% of I at I >...
  • Page 71 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 53. Sensitive directional residual overcurrent and power protection SDEPSDE Function Range or value Accuracy (0.25-200.00)% of lBase Operate level for 3I ·cosj ±1.0% of I at I £ I directional residual ±1.0% of I at I >...
  • Page 72 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 54. Thermal overload protection, one time constant LCPTTR/LFPTTR Function Range or value Accuracy Reference current (2-400)% of IBase ±1.0% of I Reference temperature (0-300)°C, (0 - 600)°F ±1.0°C, ±2.0°F...
  • Page 73 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 56. Stub protection STBPTOC Function Range or value Accuracy Operating current (5-2500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I > I...
  • Page 74 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 60. Broken conductor check BRCPTOC Function Range or value Accuracy Minimum phase current for operation (5–100)% of IBase ±1.0% of I Unbalance current operation (50–90)% of maximum current ±1.0% of I...
  • Page 75 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Voltage protection Table 61. Two step undervoltage protection UV2PTUV Function Range or value Accuracy UBase Operate voltage, low and high step (1.0–100.0)% of ±0.5% of U Absolute hysteresis (0.0–50.0)% of...
  • Page 76 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 62. Two step overvoltage protection OV2PTOV Function Range or value Accuracy Operate voltage, step 1 and 2 (1.0-200.0)% of UBase ±0.5% of U at U ≤ U ±0.5% of U at U >...
  • Page 77 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 64. Voltage differential protection VDCPTOV Function Range or value Accuracy Voltage difference for alarm and (2.0–100.0) % of UBase ±0.5% of U trip UBase Under voltage level (1.0–100.0) % of...
  • Page 78 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Frequency protection Table 67. Underfrequency protection SAPTUF Function Range or value Accuracy Operate value, start function, at symmetrical three (35.00-75.00) Hz ±2.0 mHz phase voltage Operate time, start at f + 0.02 Hz to f...
  • Page 79 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 69. Rate-of-change frequency protection SAPFRC Function Range or value Accuracy Operate value, start function (-10.00-10.00) Hz/s ±10.0 mHz/s Operate value, restore enable frequency (45.00-65.00) Hz ±2.0 mHz Definite restore time delay (0.000-60.000) s...
  • Page 80 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Multipurpose protection Table 70. General current and voltage protection CVGAPC Function Range or value Accuracy Measuring current input phase1, phase2, phase3, PosSeq, - NegSeq, -3*ZeroSeq, MaxPh, MinPh,...
  • Page 81 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 70. General current and voltage protection CVGAPC , continued Function Range or value Accuracy Independent time delay, undervoltage at 1.2 to 0.8 x U , step 1 - (0.00 - 6000.00) s...
  • Page 82 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 71. Rotor earth fault protection based on General current and voltage protection (CVGAPC) and RXTTE4 Function Range or value For machines with: • rated field voltage up to 350 V DC •...
  • Page 83 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 72. Voltage-restrained time overcurrent protection VRPVOC Function Range or value Accuracy Start overcurrent (2.0 - 5000.0)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio, overcurrent >...
  • Page 84 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Secondary system supervision Table 73. Current circuit supervision CCSSPVC Function Range or value Accuracy Operate current (10-200)% of IBase ±10.0% of I at I ≤ I ±10.0% of I at I > I Reset ratio, Operate current >90%...
  • Page 85 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 75. Fuse failure supervision VDSPVC Function Range or value Accuracy Operate value, block of main fuse (10.0-80.0)% of UBase ±0.5% of Ur failure Reset ratio <110% Operate time, block of main fuse Min.
  • Page 86 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Control Table 76. Synchronizing, synchrocheck and energizing check SESRSYN Function Range or value Accuracy Phase shift, j (-180 to 180) degrees line Voltage high limit for synchronizing and synchrocheck (50.0-120.0)% of UBase...
  • Page 87 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 77. Autorecloser SMBRREC Function Range or value Accuracy Number of autoreclosing shots 1 - 5 Autoreclosing open time: shot 1 - t1 1Ph (0.000-120.000) s ±0.2% or ±35 ms...
  • Page 88 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Scheme communication Table 78. Scheme communication logic for distance or overcurrent protection ZCPSCH Function Range or value Accuracy Scheme type Intertrip Permissive UR Permissive OR Blocking DeltaBlocking Operate voltage, Delta U (0–100)% of UBase...
  • Page 89 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 81. Scheme communication logic for residual overcurrent protection ECPSCH Function Range or value Accuracy Scheme type Permissive Underreaching Permissive Overreaching Blocking Communication scheme (0.000-60.000) s ±0.2% or ±20 ms whichever is greater coordination time Table 82.
  • Page 90 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Direct transfer trip Table 83. Low active power and power factor protection LAPPGAPC Function Range or value Accuracy Operate value, low active power (2.0-100.0)% of SBase ±1.0% of S Reset ratio, low active power <105%...
  • Page 91 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 87. Negative sequence overvoltage protection LCNSPTOV Function Range or value Accuracy Operate value, negative sequence overvoltage (1-200)% of UBase ±0.5% of U at U≤U ±0.5% of U at U>U Reset ratio, negative sequence overvoltage >95% at (10–200)% of UBase...
  • Page 92 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 89. Negative sequence overcurrent protection LCNSPTOC Function Range or value Accuracy Operate value, negative sequence overcurrent (3 - 2500)% of IBase ±1.0% of Ir at I ≤ I ±1.0% of I at I >...
  • Page 93 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 91. Three phase overcurrent LCP3PTOC Function Range or value Accuracy Operate value, overcurrent (5-2500)% of IBase ±1.0% of I at I ≤ I ±1.0% of I at I > I Reset ratio, overcurrent >...
  • Page 94 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Logic Table 93. Tripping logic common 3-phase output SMPPTRC Function Range or value Accuracy Trip action 3-ph, 1/3-ph, 1/2/3-ph Minimum trip pulse length (0.000-60.000) s ±0.2% or ±15 ms whichever is greater 3-pole trip delay (0.020-0.500) s...
  • Page 95 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 101. Number of INV instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms Table 102. Number of LLD instances Logic block Quantity with cycle time...
  • Page 96 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 109. Number of ANDQT instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms ANDQT Table 110. Number of INDCOMBSPQT instances Logic block...
  • Page 97 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 117. Number of SRMEMORYQT instances Logic block Quantity with cycle time 3 ms 8 ms 100 ms SRMEMORYQT Table 118. Number of TIMERSETQT instances Logic block...
  • Page 98 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 123. Number of IB16 instances Function Quantity with cycle time 3 ms 8 ms 100 ms IB16 Table 124. Number of ITBGAPC instances Function Quantity with cycle time...
  • Page 99 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Monitoring Table 128. Measurements CVMMXN Function Range or value Accuracy Frequency (0.95-1.05) x f ±2.0 mHz Voltage (10 to 300) V ±0.3% of U at U≤ 50 V ±0.2% of U at U>...
  • Page 100 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 131. Phase-neutral voltage measurement VNMMXU Function Range or value Accuracy Voltage (5 to 175) V ±0.5% of U at U ≤ 50 V ±0.2% of U at U > 50 V...
  • Page 101 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 136. Disturbance report DRPRDRE Function Range or value Accuracy Pre-fault time (0.05–9.90) s Post-fault time (0.1–10.0) s Limit time (0.5–10.0) s Maximum number of recordings 100, first in - first out...
  • Page 102 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 138. Insulation liquid monitoring function SSIML Function Range or value Accuracy Oil alarm level 1.00-100.00 ±10.0% of set value Oil lockout level 1.00-100.00 ±10.0% of set value Temperature alarm level -40.00-200.00...
  • Page 103 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 142. Indications Function Value Buffer capacity Maximum number of indications presented for single disturbance Maximum number of recorded disturbances Table 143. Event recorder Function Value Buffer capacity...
  • Page 104 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Metering Table 147. Pulse-counter logic PCFCNT Function Setting range Accuracy Input frequency See Binary Input Module (BIM) Cycle time for report of counter (1–3600) s value Table 148. Energy metering ETPMMTR...
  • Page 105 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Station communication Table 149. Communication protocols Function Value Protocol IEC 61850-8-1 Communication speed for the IEDs 100BASE-FX Protocol IEC 60870–5–103 Communication speed for the IEDs 9600 or 19200 Bd Protocol DNP3.0...
  • Page 106 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 155. SLM – SPA/IEC 60870-5-103/DNP3 port Quantity Range or value Optical connector Glass fiber: type ST Plastic fiber: type HFBR snap-in Fiber, optical budget Glass fiber: 11 dB (1000m/3000ft m typically *)
  • Page 107 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Remote communication Table 159. Line data communication module Characteristic Range or value Type of LDCM Short range (SR) Medium range (MR) Long range (LR) Type of fiber Graded-index Singlemode 9/125 µm...
  • Page 108 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Hardware Table 160. Case Material Steel sheet Front plate Steel sheet profile with cut-out for HMI Surface treatment Aluzink preplated steel Finish Light grey (RAL 7035) Table 161. Water and dust protection level according to IEC 60529...
  • Page 109 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Basic IED functions Table 166. Self supervision with internal event list Data Value Recording manner Continuous, event controlled List size 40 events, first in-first out Table 167. Time synchronization, time tagging...
  • Page 110 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 170. IRIG-B Quantity Rated value Number of channels IRIG-B Number of optical channels Electrical connector: Electrical connector IRIG-B Pulse-width modulated 5 Vpp Amplitude modulated – low level 1-3 Vpp –...
  • Page 111 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Inverse characteristic Table 171. ANSI Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.10 ≤ k ≤ 3.00 ANSI/IEEE C37.112 , 1.5 x I ≤ I ≤ 20 x I ±2.0% or ±40 ms...
  • Page 112 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 172. IEC Inverse time characteristics Function Range or value Accuracy Operating characteristic: 0.10 ≤ k ≤ 3.00 IEC 60255-151, ±2.0% 1.5 x I ≤ I ≤ 20 x I or ±40 ms whichever is...
  • Page 113 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 174. Inverse time characteristics for overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
  • Page 114 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 175. Inverse time characteristics for undervoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of 0.01 ±5.0% or ±45 ms whichever is greater æ...
  • Page 115 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 176. Inverse time characteristics for residual overvoltage protection Function Range or value Accuracy Type A curve: k = (0.05-1.10) in steps of ±5.0% or ±45 ms whichever is greater 0.01...
  • Page 116: Ordering For Customized Ied

    The selected qty of each table must be filled in, if no selection is possible the code is 0 Example of a complete code: RED670*2.1 - F00X00 - A00000030211111 - B5225255221255221111101000 - C3300032122020022221000300 - D22212 011 - E2220 - F4 - S6 - G232 - H20401100000 - K11111111 - L11 - M21 - P01 - B1X0 - AC -MB - B - A3X0 - D1D1ARGN1N1XXXXXXX - AAFXXX - AX...
  • Page 117 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 182. Differential functions Function Function Ordering no Positi Available Selected Notes and identification rules 1Ph High impedance differential protection HZPDIF 1MRK005904-HA Restricted earth fault protection, low impedance...
  • Page 118 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 184. Impedance functions, alternatives Function Function Ordering no Positi Available Selected Notes and identification rules Note: One, and only one alternative can be selected. Selected qty is 0 for other functions in an unselected alternative.
  • Page 119 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 186. Current functions Function Function Ordering no Positi Available Selected Notes and identification rules Instantaneous phase overcurrent protection PHPIOC 1MRK005910-AC Four step phase overcurrent protection OC4PTOC...
  • Page 120 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 193. General calculation Position Table 194. General calculation functions Function Function Ordering no Positi Available Selected Notes and identification rules Frequency tracking filter SMAIHPAC 1MRK005915-KA Table 195. Secondary system supervision Position Table 196.
  • Page 121 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 201. Logic Position Table 202. Logic functions Function Function Ordering no Positi Available Selected Notes and identification rules Configurable logic blocks Q/T 1MRK005922-MX Extension logic package 1MRK005922-AY Table 203.
  • Page 122 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 209. Mounting selection Mounting details with IP40 of protection from the front Selection Notes and Rules No mounting kit included 19" rack mounting kit for 1/2 x 19" case of 2xRHGS6 or RHGS12 19"...
  • Page 123 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 213. Analog system selection Analog system Selection Notes and Rules No first TRM included Note: Only valid in RED670–N00 Compression terminals Note: Only the same type of TRM...
  • Page 124 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 215. Binary input/output module selection Binary input/output Selection Notes and Rules modules Slot position (rear view) Note! Max 3 positions in 1/2 rack, 8 in 3/4 rack with 1TRM, 5 in 3/4 rack...
  • Page 125 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Table 215. Binary input/output module selection, continued Binary input/output Selection Notes and Rules modules SOM Static output Note: SOM must not be placed in module, 12 outputs, the following positions;...
  • Page 126: Ordering For Pre-Configured Ied

    Example code: RED670 *2.1-A30X00- A02H02-B1A3-AC-MB-B-A3X0-DAB1RGN1N1XXXXXXX-AXFXXX-AX. Using the code of each position #1-13 specified as RED670*1-2 2-3 3 3 3 3 3 3 3 3 3 3 3 3-4 4-5-6-7 8-9-10 10 10 10-110 11 11 11 11 11 11 11 11 11 11-12 12 12 12 12 12-13 13...
  • Page 127 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Software options Notes and Rules No option All fields in the ordering form do not need to be filled in High impedance differential protection Line differential protection 6 CT sets, 3-5 line...
  • Page 128 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 First local HMI user dialogue language Notes and Rules HMI language, English IEC Additional local HMI user dialogue language No additional HMI language HMI language, English US Selection for position #4.
  • Page 129 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Analog input system Notes and Rules Compression terminals Ringlug terminals First TRM, 6I+6U 1A, 100/220V First TRM, 6I+6U 5A, 100/220V First TRM, 3I, 5A + 3I, 1A + 6U, 110/220V...
  • Page 130 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Binary input/output module, mA and time synchronizating Notes and Rules boards. Make BIM with 50 mA inrush current the primary choice. BIM with 50 mA inrush current fulfill additional standards. As a consequence the EMC withstand capability is further increased.
  • Page 131 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Remote end communication, DNP serial comm. and time synchronization modules Notes and Rules Slot position (rear view) Note: The maximum number and type of LDCM modules supported...
  • Page 132: Ordering For Accessories

    1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 24. Ordering for Accessories Accessories GPS antenna and mounting details GPS antenna, including mounting kits Quantity: 1MRK 001 640-AA Cable for antenna, 20 m (Appx. 65 ft)
  • Page 133 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 External resistor unit High impedance resistor unit 1-ph with resistor and voltage dependent resistor for 20-100V operating voltage Quantity: RK 795 101-MA High impedance resistor unit 3-ph with resistor and voltage dependent resistor for 20-100V...
  • Page 134 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 User documentation Rule: Specify the number of printed manuals requested Application manual Quantity: 1MRK 505 343-UEN ANSI Quantity: 1MRK 505 307-UUS Technical manual Quantity: 1MRK 505 308-UEN...
  • Page 135 1MRK 505 346-BEN - Line differential protection RED670 2.1 IEC Product version: 2.1 Engineering manual, 670 series Quantity: 1MRK 511 355-UEN ANSI Quantity: 1MRK 511 355-UUS Cyber security guideline Quantity: 1MRK 511 356-UEN Reference information For our reference and statistics we would be pleased to be provided with the following application data:...
  • Page 137 Contact us ABB AB Substation Automation Products SE-721 59 Västerås, Sweden Phone +46 (0) 21 32 50 00 +46 (0) 21 14 69 18 www.abb.com/substationautomation...

This manual is also suitable for:

Relion rel670 2.1 iec

Table of Contents