Classification
Install
Push switch on
outdoor unit PCB
Correction
Monitor mode
[ F2 ]
Change of
function 1
Change of
function 2
Low noise
setting 1
Change of
function 3
Change of
function 4
*1 : When electricity meter No. is set to "000" and "201 to 299", the pulses input to CN135 become ineffective.
Available setting number is "001" to "200"
*2 : When the electricity meter pulse setting is set to "0000", the pulses input to CN135 become ineffective.
Available setting number is "0001" to "9999"
ITEM
Setting Mode
CODE No.
00
Pipe length setting
10
10
Forbidden
Cooling capacity shift
11
12
Heating capacity shift
13,14
Forbidden
16,17
Forbidden
20
Switching between forced stop or
emergency stop
21
Operation mode selecting method
22,23,24 Forbidden
25,26,27
Forbidden
Change of unit (Temperature)
28
29
Change of unit (Pressure)
30
Energy saving level setting
31,34,35 Forbidden
35,36,37
38,39
Capacity priority setting
40
41
Low noise mode setting
42
Low noise level setting
50,51,60,
Forbidden
61,64
70
Electricity meter No. setting 1
( Set the ones digit and tens digit of the No. of
the electricity meter connected to CN135 )*1
71
Electricity meter No. setting 2
( Set the ones digit and tens digit of the No. of
the electricity meter connected to CN135 )*1
Electricity meter pulse setting 1
72
( Set the ones digit and tens digit of the No. of
the electricity meter pulse setting connected
to CN135 )*2
Electricity meter pulse setting 2
73
7
3
( Set the ones digit and tens digit of the No. of
the electricity meter pulse setting connected
to CN135 )*2
ITEM
CODE No.
00
40-65m
01
0-40m
02
65-90m
03
90-120m
00
Factory defalt
00
Normal mode
Save energy mode +2
01
02
High power mode 1 -2
03
High power mode 2 -4
04
Forbidden
00
Normal mode
01
Save energy mode -2
02
High power mode 1 +2
03
High power mode 2 +4
00
Factory default
Factory default
00
Forced stop
00
Emergency stop
01
Priority given to the first command
00
Priority given to the external input of outdoor unit
01
0
1
Priority given to the master indoor unit
02
Factory default
00
00
Factory default
Celsius (
°C)
00
Disable (
°F)
01
00
MPa
01
psi
00
Level 1 (stop)
01
Level 2 (operated at 40% capacity)
02
Level 3 (operated at 60% capacity)
03
Level 4 (operated at 80% capacity)
Level 5 (operated at 100% capacity)
04
00
Factory default
00
Off (quiet priority)
On (capacity priority)
01
00
Off (Normal)
01
On (Low noise mode operation is always done)
Level 1
00
Level 2
01
00
Factory defalut
00~99
Setting number x00~x99
( Refer to Design & Technical Manual for details.)
00~02
Setting number 0xx~2xx
( Refer to Design & Technical Manual for details.)
00~99
Setting number xx00~xx99
( Refer to Design & Technical Manual for details.)
00~99
Setting number 00xx~99xx
( Refer to Design & Technical Manual for details.)
01-17
Information contents
°C
°C
°C
°C
°C
°C
Default
00
00
00
00