Fujitsu AUXB04GALH Service Manual page 44

Airstage j-iiil series
Hide thumbs Also See for AUXB04GALH:
Table of Contents

Advertisement

3-2-1 Operation Mode Control for Outdoor air unit
Each operation mode is controlled as below.
(1) Stop mode
Outdoor air unit fan motor : OFF
Electric expansion valve
Drain pump
Solenoid valve
(2) Cool and Heat Mode
Each operation mode is controlled as below.
Outdoor air unit
Operates according to the
fan motor
HIGH MODE setting.
Drain pump
Pulse controlled by the
Electrical
temperature difference
expansion valve
calculation and
freeze prevention control
Solenoid valve
Closed at all times
: Stop pulse
: Turns ON-OFF by the drain pump control function
: Closed
Cool
Operates according to the
HIGH MODE setting.
Turns ON-OFF by the drain pump control function
Pulse controlled by the
temperature difference.
Opened at thermostat off
and compressor on.
Closed at other operation.
Heat
Operates according to the
HIGH MODE setting.
Stop pulse
Closed at all times