Operating Condition - Fujitsu AUXB04GALH Service Manual

Airstage j-iiil series
Hide thumbs Also See for AUXB04GALH:
Table of Contents

Advertisement

Protective Function
Detect Parts
Overcurrent Break
Overcurrent
Stop
Protection Circuit
(Compressor)
Heatsink Temp
Heatsink Temp
Protection Stop
Thermistor
Frequency Maximum
Current Detector
Setting Protection
Circuit
(Compressor)
Protective function
Detect device
Outdoor Unit Reverse
Main PCB
phase, Missing phase
Reverse phase
Wire Error
prevention circuit
DISPLAY
COOL HEAT
E941
Compressor is stopped when the over currernt protectioncircuit in the
inverter PCBoad detects an abnormal current duringthe operation.
(permanent stop)
If it repeated 5 times, the compressor becomes permanentstop.
E931
Compressor is stopped when the over current protection circuit in the
inverter PC Board detects an abnormal current at the time of start up.
(permanent stop)
Compressor becomes permanent stop if it repeated over the number
of set time.
<Reset condition>
Error reset (push button SW) executed after power turned on again.
<Pattern
Heat sink temperature
<Pattern
3 minutes have elapsed and heat sink temperature
EAC4
<Pattern
Pattern
<Pattern
10 minutes have elapsed and heat sink temperature
<Pattern
Current value
<Pattern
Current value
<Pattern
Current value
<Pattern
Current value
• Pattern
temperature

Operating condition

Display
Cool Heat
< Starting condition>
1 Reverse phase prevention circuit detected reversed phase input or
input was not normal at the time of power ON.
E6 15
2 Reverse phase prevention circuit detected open-phase after power ON.
< Reset condition>
Reverse phase prevention circuit detects normal condition
Operating Condition
starting condition>
95°C
reset condition>
starting condition>
generated 3 times within 60 minutes.
reset condition>
starting condition>
Cooling: 14.8A (8,10HP) / 17.7A (12HP)
Heating: 23.5A
reset condition>
Cooling: 22.5A / Heating: 23.5A
starting condition>
Cooling:
15.8A (8,10HP) / 18.7A (12HP)
reset condition>
Cooling: 23.0A / Heating: 24.0A
and
start current value changed by outside
02-12
Operation
Compressor stopped
Compressor stopped
74°C
Compressor stopped
Error display
74°C
Compressor speed rise prohibited
Compressor speed lowered
Operation
System Stop Error indication