CHAPTER 4: SETPOINTS
845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
RANGE
Range: 0 to 1 mA, 0 to 5 mA, 0 to 10 mA, 0 to 20 mA, or 4 to 20 mA
Default: 0 to 1 mA
This setting provides the selection for the analog output range.
PARAMETER
Range: Off, any Flex Analog Parameter
Default: Off
This setting selects the measured parameter to control the Analog Output level.
MINIMUM VALUE
Range: Populates per selection of the analog parameter
Default: 0
This setting defines the minimum value of the analog output quantity. It populates
based on the selection of the analog parameter.
MAXIMUM VALUE
Range: Populates per selection of the analog parameter
Default: 0
This setting defines the maximum value of the analog output quantity. It populates
based on the selection of the analog parameter.
Each channel can be programmed to represent a FlexAnalog parameter available in the
respective 8 Series relay. The range and steps is the same as the range of the
FlexAnalog.
OUTPUTS
4–137