Control - GE 845 Instruction Manual

Transformer protection system
Hide thumbs Also See for 845:
Table of Contents

Advertisement

CHAPTER 1: INTRODUCTION

Control

845 TRANSFORMER PROTECTION SYSTEM – INSTRUCTION MANUAL
FLEXELEMENTS
Number of elements: ........................................8
Operating signal:.................................................Any analog actual value, or two values in a differential mode
Operating signal mode: ...................................Signed, or Absolute value
Operating mode: .................................................Level, Delta
Comparison direction: ......................................Over, Under
Pickup Level:..........................................................-30.000 to 30.000 pu in steps of 0.001 pu
Hysteresis:..............................................................0.1 to 50.0% in steps of 0.1%
Delta dt: ...................................................................40 msec to 45 days
Pickup and dropout delays: ...........................0.000 to 6000.000 s in steps of 0.001 s
ARC FLASH SENSOR/FIBER
Number of Point Sensors: ...............................4
Detection Radius:................................................180 degree
Maximum Fiber Length (Point Sensor): .....18 ft
Fiber Size:................................................................1000 um
Mode:........................................................................Multi-mode
Connector:..............................................................Small Media Interface (SMI)
Fiber Type:..............................................................Plastic Optical Fiber
Bend Radius: .........................................................>25 mm
BREAKER CONTROL
Operation:...............................................................Asserted FlexLogic Operands
Function: .................................................................Opens/closes, blocks, bypasses blocks to the feeder breaker
BREAKER FAILURE
Mode:........................................................................3-pole
Current Supervision: ..........................................phase and neutral current (fundamental phasor magnitude)
Current Supervision Pickup:...........................0.050 to 30.000 x CT in steps of 0.001 x CT
Current Supervision Dropout: .......................97 to 98% of pickup
Current Supervision Accuracy:.....................For 0.1 to 2.0 x CT: ± 0.5% of reading or ± 0.4% of rated
Time Delay:............................................................0.000 to 6000.000 s in steps of 0.001 s
Timer Accuracy: ..................................................± 3% of delay setting or ± ¼ cycle (whichever is greater)
Reset Time: ............................................................< 10 ms typical at 2 x Pickup at 60 Hz
LOCAL CONTROL MODE
Number of Elements: ........................................1
Select Before Operate Mode: ........................Disabled, Enabled
Mode:........................................................................Local Mode ON, Local Mode OFF
Display Status:......................................................LM (local mode) displayed in banner
Tagging:...................................................................Disabled, Enabled
SWITCH CONTROL
Operation:...............................................................Local (PB control and SLD) and Remote (asserted FlexLogic
Function: .................................................................Opens/Closes the disconnect switch
Timers: .....................................................................0.000 to 6000.000 s in steps of 0.001 s
(whichever is greater),
For > 2.0 x CT: ± 1.5% of reading
from pickup to operate
< 12 ms typical at 2 x Pickup at 50 Hz
operands)
SPECIFICATIONS
1–17

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents