Mitsubishi Electric Q03UDVCPU User Manual page 198

Qnucpu series (communication via built-in ethernet port)
Hide thumbs Also See for Q03UDVCPU:
Table of Contents

Advertisement

(4) Error
(a) An operation error occurs, the error flag (SM0) turns on, and the error code is stored
in SD0 in the following cases:
• The instruction is executed on an unsupported QnUDVCPU.
• The number of devices is incorrect.
• A device that cannot be specified was specified.
• A device using an invalid string was specified.
• The number of devices specified with
• The channel to be used by the host station is outside the setting range.
(b) The completion device ( )+1 turns on and the error code is stored in the completion
status area ( )+1 in the following cases:
• The CPU module device on another station specified by the CPU module on the host station does not exist
or the device number is outside the range.
• The IP address specified does not exist in the target.
• No cable connection is detected through the built-in Ethernet port.
• The IP address specified is not supported by the SP.WRITE instruction.
• b15 of
S1
• The target station CPU module type is outside the setting range.
• The IP address setting is outside the setting range.
• The number of resends is outside the setting range.
• The arrival monitoring time is outside the setting range.
• Length of the data to be written is outside the setting range.
196
D2
S1
+0 Instruction execution type is off.
,
, or
and exceeds the upper limit.
,
S1
S2
D1
D2
(Error code: 4002)
(Error code: 4003)
(Error code: 4004)
(Error code: 4004)
(Error code: 4101)
(Error code: 4101)
(Error code: 4031
)
H
(Error code: 4181
)
H
(Error code: 41AD
)
H
(Error code: 4182
)
H
(Error code: 41B9
)
H
(Error code: 41B9
)
H
(Error code: 41B9
)
H
(Error code: 41B9
)
H
(Error code: 41B9
)
H
(Error code: 41B9
)
H

Hide quick links: