Figure 4-23: Goose Transmission Screen
The GOOSE Transmission window has two screens.
GOOSE Tx control blocks: The user can add the required GOOSE control block.
Control Block Name: The first character in the value of this attribute must be a
letter (upper or lower case). The rest of the characters must be a number, a letter
(upper or lower case) or a "_". The maximum number of characters allowed is 32.
Description: The maximum number of characters allowed is 32.
GOOSE ID: The maximum number of characters allowed is 129.
Ethertype App ID: All characters must be numerical. The maximum number of
characters allowed is 4. IEC61850 Configurator allows characters limited to 0 to
9, A to F and it saves in the CID file the hexadecimal value (max FFFF).
Multicast MAC: 6 pairs of letters (from A to F, upper case or lower case) or
numbers separated by colons.
VLAN priority: A number from 0 to 7.
VLAN identifier: The maximum number of characters allowed is 3. IEC61850
Configurator allows characters limited to 0 to 9, A to F and it saves in the CID file
the hexadecimal value (max FFF).
Dataset sources: Each GOOSE control block can be appended with dataset items in
this screen using a drag and drop operation.
DataSet Name: The first character in the value of this attribute must be a letter
(upper or lower case). The rest of the characters must be a number, a letter (upper
or lower case) or a "_". The maximum number of characters allowed is 32.
Description: The maximum number of characters allowed is 32.