Chapter 3. INSTALLATION AND WIRING
2)
G4F-AD2A
(1)
Voltage Input
Signal source –10 ~ 10 VDC
(2)
Current Input
Signal source –20 ~ 20 mA
*1 For the cable, use a two-core twisted shielded wire.
*2 The SLD terminal and AGND terminal has to be connected.
*3 When there is much noise, the SLD terminal and FG terminal has to be grounded.
*4 Input resistance has been shown.
*5 When there is much noise, FG of the power supply module must be grounded.
Input range switch
Input range switch
3 - 4