9.1 DISTANCE ELEMENTS
Reactance difference angle = | –3.9° – 24.8° | = 28.7°  75°
Zero-sequence difference angle = | –19.8° – 0.0° | = 19.8°  75°
Negative-sequence directional difference angle = | –19.8° – 0.0° | = 19.8°  75°
Right blinder difference angle = | –93.0° – (–109.2°) | = 16.2°  90°
Left blinder difference angle = | 82.9° – 108.7° | = 25.8°  90°
Fault-type comparator difference angle = | 19.8° – 19.8° | = 0.0°  50°
All six comparators and the overcurrent supervision are satisfied.
The Quad Phase A ground element will operate for this fault.
9
9-10
D30 Line Distance Protection System
9 THEORY OF OPERATION