Faults signalled on the display The following is a list of faults that can be detected from the display and the suggestions for resolving them:
98 | © 2017 ABB | 1SDH000999R0002 - ECN000058721 - Rev. B
Signal
No Com on Local Bus
warning
Trip coil disconnected
Contact Wear PreAlarm/
Alarm
L1/L2/L3/Ne sensor
disconnected
Gext sensor Disconnected
Rating Plug Error
Internal Error
Invalid Date
CB Status Error
Rating Plug Installation
Warning
Switchboard Actors
Communication Error
Battery Low
Voltage module Installation
warning
Voltage Module Error
Software Not Compatible
(1)
Further information is available on the web site http://www.abb.com/abblibrary/DownloadCenter/, where the
procedure is available 1SDH001000R0509.
Consult the individual chapters describing the modules for fault finding and resolving with regard to Ekip Com
modules.
Suggestions
Local bus enabled bus but no module present: check connection to
terminal box modules (example: Ekip Supply, Com, Contact, ecc...)
Check the connection of the opening solenoid
Make sure that the contacts/poles are in good condition.
Check the connection of the current sensor
Check the connection of the current sensor
Check the connection of the Rating Plug on the front of the trip unit and
verify that the protections do not cause parameter configuration conflicts
Contact ABB
Set the date
Check the circuit-breaker status signal contacts
Install Rating Plug, and in the case of faults check its connection
Check the configuration and connection of the Ekip Link modules
Change the battery on the trip unit
Install the module
Error reading the module parameters. Contact ABB
The Mainboard and Ekip Touch software versions are not compatible with
each other: editing of all parameters is inhibited by the display.
The protections L, I and Iinst are active and working with the parameters
set in the previous protection trip unit.
To restore compatibility please contact ABB.
Putting into service and maintenance | 2 - Identification of alarms or failures
ABB | SACE Emax 2