CHAPTER 7: COMMANDS AND TARGETS
FIRMWARE LOCK
Message: "Unauthorized firmware attempt"
Latched target message: No.
Description of problem: A firmware upgrade operation was attempted while the lock relay setting was enabled.
What to do: Ask the Supervisor to unlock the relay and try again.
SETTING LOCK
Message: "Unauthorized setting write"
Latched target message: No.
Description of problem: A setting write was attempted while the lock relay setting was enabled.
What to do: Ask the Supervisor to unlock the settings and try again.
SERVER UNAVAILABLE
Message: "An attempt to contact the Radius server has failed"
Latched target message: No.
Description of problem: The RADIUS authentication server is unavailable.
What to do: Verify network connectivity and try again.
DOS PARTITION ALARM:
SELF-TEST ERROR
Description of problem: There is a problem with the Compact Flash memory in the CPU module.
How often the test is performed: On relay power-up and afterwards once every 24 hours.
What to do: Contact the factory.
PROTOTYPE FIRMWARE:
Self Test Error
Description of problem: Seen until the builds is tagged as being 'release candidate' or 'gold' builds.
What to do: Update firmware to either of these builds.
7.2.2.4 External device self-test error messages
The major self-test errors are listed and described below.
GPM-F FAILURE:
TROUBLE 01
Latched target message: No.
Description of problem: The G60 detects loss of communication with the field ground module on the RS485 link.
How often the test is performed: Every five seconds.
What to do: Check the field ground module and its RS485 connection to G60.
GPM-F FAILURE:
TROUBLE 02
Latched target message: No.
G60 GENERATOR PROTECTION SYSTEM – INSTRUCTION MANUAL
TARGETS MENU
7
7-13