GE L30 Instruction Manual page 360

Line current differential system, ur series
Hide thumbs Also See for L30:
Table of Contents

Advertisement

5.8 INPUTS AND OUTPUTS
On the two-terminal, two channel system (redundant channel), direct outputs 1-1 to 1-8 are send over both chan-
nels simultaneously and are received separately as direct inputs 1-1 to 1-8 at channel 1 and direct inputs 2-1 to 2-8
NOTE
at channel 2. Therefore, to take advantage of redundancy, the respective operands from channel 1 and 2 can be
ORed with FlexLogic™ or mapped separately.
b) DIRECT INPUTS

PATH: SETTINGS
INPUTS/OUTPUTS
 DIRECT INPUTS
5
The
DIRECT INPUT 1-1(8) DEFAULT
just completed startup or the local communications channel is declared to have failed. Setting
to "On" means that the corresponding local FlexLogic™ operand (
or during communications channel failure. When the channel is restored, the operand logic state reflects the actual state of
the corresponding remote direct output.
c) DIRECT OUTPUTS
PATH: SETTINGS
INPUTS/OUTPUTS
 DIRECT OUTPUTS
The relay provides eight direct outputs that are conveyed on communications channel 1 (numbered 1-1 through 1-8) and
eight direct outputs that are conveyed on communications channel 2 (numbered 2-1 through 2-8). Each digital point in the
message must be programmed to carry the state of a specific FlexLogic™ operand. The setting above is used to select the
operand which represents a specific function (as selected by the user) to be transmitted.
5-216

DIRECT
DIRECT INPUTS
DIRECT INPUT 1-1
DEFAULT: Off
DIRECT INPUT 1-2
MESSAGE
DEFAULT: Off
DIRECT INPUT 1-8
MESSAGE
DEFAULT: Off
DIRECT INPUT 2-1
MESSAGE
DEFAULT: Off
DIRECT INPUT 2-2
MESSAGE
DEFAULT: Off
DIRECT INPUT 2-8
MESSAGE
DEFAULT: Off
setting selects the logic state of this particular bit used for this point if the local relay has


DIRECT
DIRECT OUTPUTS
DIRECT OUTPUT 1-1:
Off
DIRECT OUTPUT 1-2:
MESSAGE
Off
DIRECT OUTPUT 1-8:
MESSAGE
Off
DIRECT OUTPUT 2-1:
MESSAGE
Off
DIRECT OUTPUT 2-2:
MESSAGE
Off
DIRECT OUTPUT 2-8:
MESSAGE
Off
L30 Line Current Differential System
Range: Off, On
Range: Off, On
Range: Off, On
Range: Off, On
Range: Off, On
Range: Off, On
) will have logic state "1" on relay startup
DIRECT I/P 1-1(8)
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
5 SETTINGS
DIRECT INPUT 1-1(8) DEFAULT
GE Multilin