12. Backup Operation
12. Backup Operation
Alarm list 2 (Backup operation continues as long as the problem is not solved.)
Alarm display
F04
Discharge temperature sensor failure for compressor 1
F05
Discharge temperature sensor failure for compressor 2
F06
Gas temperature sensor in heat exchanger 1
1
F07
Liquid temperature sensor in heat exchanger 1
F08
Ambient air temperature
F12
Suction temperature
Temp. sensor at refrigerant gas outlet of dual-tube
F14
F16
High pressure sensor failure
F17
Low pressure sensor failure
F23
Gas temperature sensor in heat exchanger 2
F24
Liquid temperature sensor in heat exchanger 2
H05
Compressor 1 discharge temperature sensor disconnected
H08
Oil temperature sensor 1 (Inverter compressor)
H13
Compressor 2 CT sensor disconnected or short-circuit
H15
Compressor 2 discharge temperature sensor disconnected
Compressor 3 CT sensor disconnected or short-circuit
H23
H25
Compressor 3 discharge temperature sensor disconnected
H27
Oil temperature sensor 2 (Constant-speed compressor 1)
H28
Oil temperature sensor 3 (Constant-speed compressor 2)
P03
Compressor 1 discharge temperature trouble
P17
Compressor 2 discharge temperature trouble
Compressor 3 discharge temperature trouble
P18
A :
When there is one outdoor unit in the system, only compressor that has sensor failure stops.
When there are multiple outdoor units in the system, only the outdoor unit which contains the problem
stops but the other outdoor units in the system operate normally.
B :
When there is one outdoor unit in the system, the backup operation does not work.
When there are multiple outdoor units in the system, only the outdoor unit which contains the problem
stops but the other outdoor units in the system operate normally.
* Backup operation caused by an alarm listed in "alarm list 2" will finish automatically after 24 hours if the same
alarm does not occur again for 24 hours.