Floor Protector Requirements - Pioneer Metro Installation & Owner's Operation Manual

Insert wood fires
Table of Contents

Advertisement

Floor protector requirements

Floor protector requirements
Metro fireplace inserts are designed to be installed directly onto a concrete
base. The floor protector is required to project in front of the Metro and
must extend a minimum of 200mm to each side of the door opening
making the minimum floor protector width 825mm.
The floor protector must project from behind the fascia the distance
specified (I) in the table below. Minimum projection is the distance from
the front of the wall lining (behind the fascia) to the front non combustible
point of the floor protector.
ECO Trend Insert
On properties less than 2 hectares, the ECO Trend Insert must be installed
with the single speed Metro thermo fan.
The ECO Trend Insert requires an ash-hearth floor protector with
recommended construction of tiles on 6mm thick non combustible board.
The minimum floor protector projection forward of the Metro is 300mm as
detailed in the table below. Any non-combustible material fixed directly to a
combustible floor is acceptable.
LTD Trend Insert
The LTD Trend Insert requires an insulating floor protector. The forward
projection is dependent on the height of the fireplace insert above the
combustible floor. The schedule of projections listed for heights of 0mm
to 41mm+ can be achieved by the thickness of the floor protector, raising
the Insert or a combination of the two. Recommended construction is tiled
eterpan with a combined thickness as detailed in the table below.
Insert & Built-In Dimensions (mm)
ECO Trend Insert
LTD Trend Insert
Smart Insert
LTD Smart Insert
Please note: All measurements detailed above exclude the 13mm insulating blanket.
Floor Protector Heights
ECO Trend Insert - DIMENSION I
LTD Trend Insert - DIMENSION I
Smart Insert - DIMENSION I
LTD Smart Insert - DIMENSION I
A
B
560
500
550
560
500
550
560
495
550
560
495
550
0mm
10mm
15mm
300mm minimum projection is required irrespective of the height of the floor protector
455mm
455mm
445mm
395mm
371mm
371mm
395mm
371mm
371mm
Smart Insert
The ECO Smart Insert requires an insulating floor protector with
recommended construction of tiles on 26mm thick eterpan or alternative
insulating material of equivalent insulation properties. The forward
projection detailed below (I) is dependent on the height of the fireplace
insert above the combustible floor.
LTD Smart Insert
The LTD Smart Insert requires an insulating floor protector with
recommended construction of tiles on 26mm thick eterpan or alternative
insulating material of equivalent insulation properties. The forward
projection detailed below (I) is dependent on the height of the fireplace
insert above the combustible floor.
Mantel clearance
A timber or combustible mantel shelf above the fireplace Insert opening
should be a minimum distance (L) above the top of the Metro's fascia
as detailed in the table below. If the clearance is less than the minimum
specified, a deflector or heat shield will be required to be fitted under the
mantelshelf or to the top of the fascia using the relevant detail as set out in
AS/NZS 2918:2001.
ECO Trend & LTD Trend Insert
Refer table below
(Dimension I)
C
D
E
F
405
810
185
405
810
185
405
890
30
405
890
30
20mm
25mm
436mm
424mm
353mm
353mm
353mm
353mm
Smart Insert models
Refer table below
(Dimension I)
G
H
I
J
650
825
300
170
650
825
350
170
672
825
312
130
672
825
312
130
30mm
35mm
40mm
408mm
396mm
366mm
332mm
332mm
312mm
332mm
332mm
312mm
K
L
360
340
360
460
325
475
325
475
41mm+
350mm
312mm
312mm
5