5 SETTINGS
PATH: SETTINGS
SYSTEM SETUP
BREAKER 1
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
MESSAGE
GE Multilin
N60 Network Stability and Synchrophasor Measurement System
BREAKERS
BREAKER 1(6)
BREAKER 1
FUNCTION: Disabled
BREAKER1 PUSH BUTTON
CONTROL: Disabled
BREAKER 1 NAME:
Bkr 1
BREAKER 1 MODE:
3-Pole
BREAKER 1 OPEN:
Off
BREAKER 1 BLK OPEN:
Off
BREAKER 1 CLOSE:
Off
BREAKER 1 BLK CLOSE:
Off
BREAKER 1 ΦA/3P CLSD:
Off
BREAKER 1 ΦA/3P OPND:
Off
BREAKER 1 ΦB CLOSED:
Off
BREAKER 1 ΦB OPENED:
Off
BREAKER 1 ΦC CLOSED:
Off
BREAKER 1 ΦC OPENED:
Off
BREAKER 1 Toperate:
0.070 s
BREAKER 1 EXT ALARM:
Off
BREAKER 1 ALARM
DELAY:
0.000 s
MANUAL CLOSE RECAL1
TIME:
0.000 s
BREAKER 1 OUT OF SV:
Off
BREAKER 1 EVENTS:
Disabled
5.4 SYSTEM SETUP
Range: Disabled, Enabled
Range: Disabled, Enabled
Range: up to 6 alphanumeric characters
Range: 3-Pole, 1-Pole
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic™ operand
Range: 0.000 to 65.535 s in steps of 0.001
Range: 0.000 to 65.535 s in steps of 0.001
Range: FlexLogic™ operand
Range: Disabled, Enabled