6 IEC FUNCTIONS
6 - 62
Argument Type
ST Program
BOOL
b_result := EQ_E( b_select,
X10, X11, X12, M20 );
STRING
b_result := EQ_E( b_select,
s_ary1, s_ary2, b_data1 );
Conversion Result
LD
X10
AND
X11
LDI
X10
ANI
X11
ORB
LD
X11
AND
X12
LDI
X11
ANI
X12
ORB
ANB
OUT
M8191
LD
b_select
AND
M8191
SET
M20
LD
b_select
ANI
M8191
RST
M20
LD
b_select
OUT
b_result
LD$=
s_ary1 s_ary2
OUT
M8191
LD
b_select
AND
M8191
SET
b_data1
LD
b_select
ANI
M8191
RST
b_data1
LD
b_select
OUT
b_result
For the usable data type, refer to "3.2.2 About ANY type".
Used Instruction
LD,AND,LDI,ANI,
ORB,ANB,SET,RST
LD$=,OUT,LD,AND,
SET,ANI,RST
6 - 62