ABB AMVAC Installation And Operation Manual page 17

Medium voltage vacuum circuit breakers
Hide thumbs Also See for AMVAC:
Table of Contents

Advertisement

8
6
5
7
Figure 2a: Circuit breaker front with controls
1
Breaker enclosure
1.1 Front Plate
1.2 Lifting bracket, both sides
2
"Ready" indicator
3
CLOSE push-button
4
OPEN push-button
5
Mechanical operating cycle counter
6
Mechanical CLOSE/OPEN indicator
7
Rating plate
8
Socket for emergency open operation
lever
8
28
10
5
6
Figure 2c: View of the magnetic actuator mechanism and
auxiliary systems with the front cover removed
5
Mechanical operating cycle counter
6
Mechanical switch position indicator
10 Actuator
26 Storage Capacitors
27 Circuit breaker control unit (ED2 board)
28 Auxiliary switches
STRUCTURE AND FUNCTION
1.1
1
1.2
2
3
4
1VAL050601-MB Rev C
Figure 2b: Sectional view of a circuit breaker type,
AMVAC schematic diagram
1
Circuit breaker enclosure
1.1
Front panel, removable
9
Emergency manual opening
mechanism
10
Magnetic actuator
11
OPEN coil
12
Magnet armature
13
Permanent magnets
14
CLOSE coil
17
Stroke adjuster
18
Lever shaft
19
Insulated link rod
20
Contact force spring
21
Flexible connector
22
Lower breaker terminal
23
Cast insulation
24
Vacuum interrupter
24.1 Moving Contact
24.2 Fixed Contact
25
Upper breaker terminal
27
26
6
Figure 2d: Switch position indicator
6
Mechanical switch position indicator
15
Sensor for "Circuit-breaker OPEN" signal
16
Sensor for "Circuit-breaker CLOSED"
signal
2
15
3
16
4
17

Advertisement

Table of Contents
loading