OPERATION, INSTALLATION, AND MAINTENANCE
I
:
NTERLOCKS
The AMVAC™ circuit breaker contains a number of interlocks. A description of each interlock follows as encountered
during racking of the circuit breaker into the compartment.
I
B
NTERFERENCE
LOCKING
under rated circuit breakers from being inserted into higher rated compartments.
continuous current, interrupting current, close and latch capability, and maximum voltage.
P
P
OSITIVE
OSITION FOR
extended into the compartment slots.
P
P
OSITIVE
OSITION FOR
compartment by blocking withdrawal of the locking tabs. The handle release pin blocks the handles unless the circuit
breaker is in the Disconnect position.
MODIFICATION
CONDITIONS TO PERSONNEL AND EQUIPMENT. DO NOT OVERRIDE, BY-
PASS OR ADJUST INTERLOCKS.
P
I
OSITION
NTERLOCKS
breaker in any direction from any positive position (Disconnect, Test, or Connect). The release lever is blocked from
actuation when the circuit breaker is CLOSED. The ability to close the circuit breaker is blocked mechanically and elec-
trically unless it is in one of the three positive positions. If the circuit breaker is in between positions, the remote close
signal and front panel close signal are disengaged and the circuit breaker cannot be closed.
M
O
ANUAL
PERATION
(Refer to Table 2, Appendix A, and Fig. 8)
The circuit breaker can be operated manually (opening only) or electrically. The manual Opening Handle is required for

manual operation.

1. Inspect the initial state of the circuit breaker to determine the operations available (Refer to Table 1 and Fig. 2)
a. Close/Open indicator (6)
b. Stored Energy Charged/Discharged "Ready" Indicator (2)
2. Manual opening may be performed in any position, but should be avoided when the circuit breaker is in the Connect
position. Any manual operation while the circuit breaker is racked onto live bus should be avoided to insure added
safety to the operator.
Inside the breaker there are stored energy capacitors that must be discharged prior to removing the
front cover of the breaker. Wait 20 minutes after breaker removal from the cell prior to removing the
front cover of the breaker for the discharging of the storage capacitors to occur.
18
:
A interference blocking plate (Fig. 1) in the circuit breaker compartment prevents
R
:
ACKING
The racking mechanism is blocked unless the interlock tabs are fully
R
:
EMOVAL
The handle release pin prevents withdrawing the circuit breaker from the
TO

INTERLOCKS

:
The position release lever must be depressed in order to begin racking the circuit
:
(Opening)
1VAL050601-MB Rev C
DANGER
CAN
RESULT
DANGER
The code plate rating includes
IN
HAZARDOUS

Advertisement