ABB TTH300 Safety Instructions

Temperature transmitter, sill 2 / 3
Hide thumbs Also See for TTH300:

Advertisement

SIL-Safety Instructions
Temperature Transmitter
SM/TTX200/TTX300/SIL-EN
TTH200, TTR200, TTH300, TTF300, TTF350
Information about functional safety

Advertisement

Table of Contents
loading

Summary of Contents for ABB TTH300

  • Page 1 SIL-Safety Instructions Temperature Transmitter SM/TTX200/TTX300/SIL-EN TTH200, TTR200, TTH300, TTF300, TTF350 Information about functional safety...
  • Page 2 Phone: +49 180 5 222 580 Fax: +49 621 381 931-29031 automation.service@de.abb.com © Copyright 2010 by ABB Automation Products GmbH Subject to changes without notice This document is protected by copyright. It assists the user in safe and efficient operation of the device.
  • Page 3: Table Of Contents

    Measuring point for SIL 2 – Single configuration ..................10 Measuring point for SIL 3 – Dual configuration ....................11 Periodic checks ............................12 Configuration..............................13 Safety engineering parameters.........................16 Namur NE 93 ...............................17 Management summary FMEDA – Failure modes, effects, and diagnostic analysis ......18 SM/TTX200/TTX300/SIL-EN TTH200, TTR200, TTH300, TTF300, TTF350...
  • Page 4: Field Of Application

    IEC 61508. The operating limits are defined in the data sheets and operating instructions for the separate models. In case of questions, please contact your ABB partner. Acronyms and abbreviations Acronym /...
  • Page 5 In multidrop mode, up to 15 field devices are connected in parallel to a single wire pair. The analog current signal simply serves to supply power to the devices in two-wire technology with a fixed current of ≤ 4 mA. SM/TTX200/TTX300/SIL-EN TTH200, TTR200, TTH300, TTF300, TTF350...
  • Page 6 In this configuration the two current signals 4 … 20 mA have to be evaluated accordingly by the downstream logics unit (a DCS, for example). This results in an HFT = 1 (1oo2 architecture) for corresponding SIL3. TTH200, TTR200, TTH300, TTF300, TTF350 SM/TTX200/TTX300/SIL-EN...
  • Page 7: Relevant Standards

    Operating instructions TTF350 CI/TTF350 Commissioning instructions The documents can be downloaded in the available languages from the ABB website at "www.abb.com/temperature". In addition, the user of this device is responsible for ensuring compliance with applicable legal regulations and standards. SM/TTX200/TTX300/SIL-EN...
  • Page 8: Terms And Definitions

    A specified function that is carried out by a safety-related system functions with the goal, under consideration of a defined dangerous incident, of achieving or maintaining a safe state for the system. Example: limit temperature monitoring. TTH200, TTR200, TTH300, TTF300, TTF350 SM/TTX200/TTX300/SIL-EN...
  • Page 9: Safety Function

    Safety function Safety function TTH200-.H, TTR200-.H, TTH300-.H, TTF300-.H, and TTF350-.H transmitters generate a linear temperature unit signal of 4 ... 20 mA. All safety functions refer strictly to the analog output signal. The entire valid range for the output signal must be configured between min. 3.8 mA and max.
  • Page 10: Measuring Point For Sil 2 - Single Configuration

    When the safety function is being checked Warning! The device's safety function includes the basic device TTH200-.H, TTR200-.H, TTH300-.H, TTF300-.H, and TTF350-.H with connected sensor, inclusive of the housing and the process connections used. The information in the corresponding documentation must be taken into consideration.
  • Page 11: Measuring Point For Sil 3 - Dual Configuration

    B Transmitter 1 G Transmitter 2 C DCS H Measuring circuit 2 D Measuring circuit 1 E Interface for LCD indicator Important The safety-relevant technical parameters are specified in the SIL declaration of conformity. SM/TTX200/TTX300/SIL-EN TTH200, TTR200, TTH300, TTF300, TTF350...
  • Page 12: Periodic Checks

    The sensor has to be tested in accordance with the SIL requirements of the customer application. SensyTemp TSP temperature sensors can be tested in accordance with the OI/TSP by means of a quick check. TTH200, TTR200, TTH300, TTF300, TTF350 SM/TTX200/TTX300/SIL-EN...
  • Page 13: Configuration

    To implement this, proceed as follows: Activating / Deactivating write protection 1. TTH300-.H, TTF300-.H, and TTF350-.H via the LCD display with local keyboard Go to "Device Setup", "Write Protection" and enter a password other than "0110" to activate write protection. Enter the password "0110" to disable write protection (see the operating instructions).
  • Page 14 Checks: Write protection must be checked as follows: 1. TTH300-.H, TTF300-.H, and TTF350-.H locking via the LCD display with local keyboard Check whether the lock icon is displayed on the LCD display. Select the "Fault Signaling" menu and make sure the edit icon is not showing on the LCD display.
  • Page 15 • Drift duration Maximum 120 s Sensor type freestyle characteristic and Callendar-Van Dusen on the TTH300-.H, TTF300-.H, and TTF350-.H When using these two configurations, it is necessary to check at least 3 reference points to verify the configured characteristic. For complex curves, check more reference points according to complexity.
  • Page 16: Safety Engineering Parameters

    Safety engineering parameters Safety engineering parameters The safety-relevant technical parameters are specified in the SIL declaration of conformity. TTH200, TTR200, TTH300, TTF300, TTF350 SM/TTX200/TTX300/SIL-EN...
  • Page 17: Namur Ne 93

    Namur NE 93 10 Namur NE 93 TTH200-.H, TTR200-.H, TTH300-.H, TTF300-.H, TTF350-.H transmitters meet requirements according to Namur NE 93. SM/TTX200/TTX300/SIL-EN TTH200, TTR200, TTH300, TTF300, TTF350...
  • Page 18: Management Summary Fmeda - Failure Modes, Effects, And Diagnostic Analysis

    Management summary FMEDA – Failure modes, effects, and diagnostic analysis 11 Management summary FMEDA – Failure modes, effects, and diagnostic analysis TTH200, TTR200, TTH300, TTF300, TTF350 SM/TTX200/TTX300/SIL-EN...
  • Page 19 Management summary FMEDA – Failure modes, effects, and diagnostic analysis SM/TTX200/TTX300/SIL-EN TTH200, TTR200, TTH300, TTF300, TTF350...
  • Page 20 Management summary FMEDA – Failure modes, effects, and diagnostic analysis TTH200, TTR200, TTH300, TTF300, TTF350 SM/TTX200/TTX300/SIL-EN...
  • Page 21 Management summary FMEDA – Failure modes, effects, and diagnostic analysis SM/TTX200/TTX300/SIL-EN TTH200, TTR200, TTH300, TTF300, TTF350...
  • Page 22 Management summary FMEDA – Failure modes, effects, and diagnostic analysis TTH200, TTR200, TTH300, TTF300, TTF350 SM/TTX200/TTX300/SIL-EN...
  • Page 23 Management summary FMEDA – Failure modes, effects, and diagnostic analysis SM/TTX200/TTX300/SIL-EN TTH200, TTR200, TTH300, TTF300, TTF350...
  • Page 24 ABB has Sales & Customer Support expertise in over The Company’s policy is one of continuous product 100 countries worldwide. improvement and the right is reserved to modify the information contained herein without notice. www.abb.com/temperature Printed in the Fed. Rep. of Germany (03.2010) ©...

This manual is also suitable for:

Ttf300Tth200Ttr200Ttf350

Table of Contents