...4.2 Set Up Totalizer

CUtOFF
0
PrESEt
tOtL –
0000
0000
PrEdEt
tOtL –
9999
9999
Cut-off Level
Set the lowest value at which the totalizer is to stop counting (in engineering units).
Example – On differential pressure flow, the inaccuracy of the system at very low flow rates may
cause large accumulative totalizer errors due to erroneous counts. If a cut-off level is set above
the point where these erroneous counts occur they are ignored.
Preset Value
If the
(batch) flow total is reset it reverts to the value set at this frame.
OPERATOR LEVEL
Set the value for the first digit using the
switch to advance the flashing cursor (
Advance to next digit.
/
Set the value for the second digit.
Advance to next digit.
Repeat the above procedure for the remaining digits.
Predetermined
Value
0045
0000
Count Up
0000
0000
Preset Value
Note. The setting of the
CNtdIr-UP
(incremental counter) –
CNtdIr-dN
(decremental counter) –
Predetermined Value
If the wrap-around facility is used (see below), the front panel total is automatically reset to the
once the
Preset Value
Predetermined Value
front panel total stops when the
Set the value for the first digit using the
switch to advance the flashing cursor (
Advance to next digit.
/
Set the value for the second digit.
Advance to next digit.
Repeat the above procedure for the remaining digits.
Continued on next page

4 ADVANCED CONFIGURATION LEVEL...

/
switches. The value is changed by using the
_
) and altering each digit in turn.
Wrap Off stops counting
Preset Value
at Predetermined Value.
0085
Wrap Pulse transmitted.
0000
Predetermined Value
Wrap Pulse Transmitted
Count Down
0000
0000
Predetermined
Value
and
Preset
Predetermined Values
Preset Value
Preset Value
is reached. If the wrap-around facility is not used, the
is reached.
Predetermined Value
/
switches. The value is changed by using the
_
) and altering each digit in turn.
• Totalization
Wrap On resets to Preset
Value once Predetermined
Value is reached. Wrap
Pulse transmitted.
Transmitted
Wrap On
Wrap Off
Preset Value
Preset Value
is dictated by the
Count Direction
<
Predetermined Value
>
.
Predetermined Value
Wrap Pulse
Resets To
:
15