Digital Input And Relay Output Terminals - ABB ACS800-07-0610-3 Hardware Manual

Acs800-07 series 500 to 2800 kw
Table of Contents

Advertisement

Digital input and relay output terminals

The DSU can be controlled through two control interfaces: local and remote. The
operation switches placed on the cabinet door are connected to the local control
interface. The remote control interface can be used in parallel when control by other
external devices is needed.
S11
S11
1
1
3
0
2
4
0
1
START
S21
S21
X1
13
X2
14
0
1
Digital input data
Input voltage: "1" = 15...48 VDC or
15...230 VAC. All inputs must be of the
same type (AC or DC).
Internal connection:
DI
Relay output data
Contact rating:
230 VAC / 1 A continuous
Internal connection:
RO
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
DSSB board terminals
ST
X10
Local digital inputs
1
START
2
ON
3
+24 V
4
RESET
5
RESET LED Ground for reset button LED
6
+24 V
X5
Remote digital inputs
1-2
ON
3-4
START
5-6
RESET
7-8
EXT.FAULT 1: External fault. DSU trips. 0: No external fault.
X6
Relay outputs
1-2
RO1
3
4-5
RO2
X7
Relay outputs
1-2
RO3
3
4-5
RO4
6
7-8
RO5
1)
After the power switch-on, the DSU first charges the contactor control
capacitors (~ 3 s at first start) and checks the fault status. DSU starts rectifying
only after the contactors are closed by the START input.
2)
These DSSB board terminals are wired to a separate terminal block to which
the user connections are to be made. See the circuit diagrams delivered with the
unit.
0 -> 1: DSU closes main contactors and starts rectifying.
Note: Local ON input must be switched on.
1)
1: DSU is rectifying.
0: DSU stops rectifying and opens
contactors.
+24 VDC
0 -> 1: Reset
+24 VDC
2)
1)
1: DSU is rectifying.
0: DSU stops rectifying and opens
contactors. Note: If start command was given through local
START input, DSU stops only after local ON input is
switched off.
0 -> 1: DSU closes main contactors and starts rectifying.
Note: Local and remote ON inputs must be switched on.
0 -> 1: Reset
2)
Off: Fault
-
On: Running
2)
Overtemperature warning
-
Off: Earth (ground) fault detected
-
Off: Emergency stop acknowledgement to inverter