Connections and tap settings of the auxiliary voltage transformer
3~ input
Supply
Terminals
voltage
A1 to... B1 to... C1 to...
690 V
A1, B1, C1
C2
660 V
A1, B1, C1
C2
600 V
A1, B1, C1
C3
575 V
A1, B1, C1
C3
525 V
A1, B1, C1
C4
500 V
A1, B1, C1
C4
480 V
A1, B1, C1
C5
460 V
A1, B1, C1
C5
440 V
A1, B1, C1
C6
415 V
A1, B1, C1
C6
400 V
A1, B1, C1
C7
380 V
A1, B1, C1
C7
Installation of brake resistors
See the chapter
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
Output
Tap settings
Supply
voltage
A2
B2
690 V
A2
B2
660 V
A3
B3
600 V
A3
B3
575 V
A4
B4
525 V
A4
B4
500 V
A5
B5
480 V
A5
B5
460 V
A6
B6
440 V
A6
B6
415 V
A7
B7
400 V
A7
B7
380 V
Resistor
braking.
3~ Input
1~ output
230 V
Terminals
Tap setting
Terminals
a3, n1
230–
a4, n1
a3, n1
230+
a4, n1
a3, n1
230–
a4, n1
a3, n1
230+
a4, n1
a3, n1
230–
a4, n1
a3, n1
230+
a4, n1
a3, n1
230–
a4, n1
a3, n1
230+
a4, n1
a3, n1
230–
a4, n1
a3, n1
230+
a4, n1
a3, n1
230–
a4, n1
a3, n1
230+
a4, n1
3~ output
115 V
400 V (50 Hz)
Tap setting
Terminals
115–
a1, b1, c1
115+
a1, b1, c1
115–
a1, b1, c1
115+
a1, b1, c1
115–
a1, b1, c1
115+
a1, b1, c1
115–
a1, b1, c1
115+
a1, b1, c1
115–
a1, b1, c1
115+
a1, b1, c1
115–
a1, b1, c1
115+
a1, b1, c1
Electrical installation
89
320 V (60 Hz)
Terminals
a2, b2, c2
a2, b2, c2
a2, b2, c2
a2, b2, c2
a2, b2, c2
a2, b2, c2
a2, b2, c2
a2, b2, c2
a2, b2, c2
a2, b2, c2
a2, b2, c2
a2, b2, c2