MES interface module
■Module-specific backup parameter
The module-specific backup parameter is not provided, and thus no data is backed up.
■Precautions
Stop all communications of the MES Interface Function Configuration Tool to the module before executing the online module
change, because when the online module change is executed, communication with the MES Interface Function Configuration
Tool is also stopped. (Errors may occur in the MES Interface Function Configuration Tool.)
High speed data logger module
■Module-specific backup parameter
The module-specific backup parameter is not provided, and thus no data is backed up.
■Precautions
Stop all communications of the High Speed Data Logger Module Configuration Tool to the module before executing the online
module change, because when the online module change is executed, communication with the High Speed Data Logger
Module Configuration Tool is also stopped. (Errors may occur in the High Speed Data Logger Module Configuration Tool.)
C intelligent function module
■Module-specific backup parameter
The module-specific backup parameter is not provided, and thus no data is backed up.
■Backup and restoration of data in the module
• Note the setting contents of service/account settings of the engineering tool before starting the online module change. For
the service/account settings on the new module to be mounted, prepare a separate system and set the settings in the
separate system.
• Before starting online module change, carry out back up and restoration using the FTP client software. Perform back up on
the module that is subject to online module change; perform restoration on the new module to be mounted in online module
change. For the restoration, prepare a separate system and perform restoration there.
OPC UA server module
■Module-specific backup parameter
The module-specific backup parameter is not provided, and thus no data is backed up.
■Precautions
Stop all communications of the MX OPC UA Module Configurator-R and OPC UA client to the module before executing the
online module change, because when the online module change is executed, communication with the MX OPC UA Module
Configurator-R and OPC UA client is also stopped. (Errors may occur in the MX OPC UA Module Configurator-R and OPC UA
client.)
3 REPLACEMENT PROCEDURE
26
3.1 Specifications