Setting Sample Of Related Parameters - Toshiba TOSVERT VF-S15 Instruction Manual

Functions for lift application
Hide thumbs Also See for TOSVERT VF-S15:
Table of Contents

Advertisement

4.3 Setting sample of related parameters

Comm.
Title
Number
cmod
Command mode selection
0003
fmod
Frequency setting mode selection 1 0 - 14
0004
acc
Acceleration time 1
0009
dec
Deceleration time 1
0010
fh
Maximum frequency
0011
ul
Upper limit frequency
0012
ll
Lower limit frequency
0013
pt
V/F control mode selection
0015
sr1
Preset speed operation frequency 1 ll - ul
0018
sr2
Preset speed operation frequency 2 ll - ul
0019
f131
Output terminal selection 2A (OUT) 0 - 255
0131
f240
Starting frequency
0240
f304
Dynamic braking selection
0304
Overvoltage limit operation
f305
0305
(Deceleration stop mode selection)
f308
Dynamic braking resistance
0308
Dynamic braking
f309
0309
resistor capacity
Brake releasing waiting time
f325
0325
Brake releasing small current
f326
0326
detection level
f340
Creeping time 1
0340
f341
Braking mode selection
0341
f342
Load portion torque input selection
0342
Hoisting torque bias input (valid
f343
0343
only when f342=4)
f344
Lowering torque bias multiplier
0344
f345
Brake release time
0345
f346
Creeping frequency
0346
f347
Creeping time 2
0347
f348
Braking time learning function
0348
f400
Auto-tuning
0400
f401
Slip frequency gain
0401
f402
Automatic torque boost value
0402
f405
Motor rated capacity
0405
f415
Motor rated current
0415
f417
Motor rated speed
0417
Power running stall continuous trip
f452
0452
detection time
f460
Speed loop gain
0460
f462
Speed reference filter coefficient
0462
(*1) Default setting values vary depending on the setup menu setting.
(*2) Default setting values depend on inverter's capacity. Refer to the instruction manual about the default
setting values.
Functions
Setting range
0 - 4
0.0 - 3600 (s)
0.0 - 3600 (s)
30.0 - 500.0(Hz)
0.5 - fh (Hz)
0.0 - ul (Hz)
0 - 8
0.1 - 10.0 (Hz)
0 - 4
0 - 3
1.0 - 1000 ohm
0.01 - 30.00kW
0.00-2.50 (s)
0-100 (%)
0.00 - 10.00 (s)
0 - 3
0 - 4
-250 - 250%
0 - 100%
0.00 - 10.00 (s)
f240 - 20.0Hz
0.00 - 10.00 (s)
0, 1
0 - 5
0 - 250(%)
0.1 - 30.0(%)
0.01 - 22.00kW
0.1 - 100.0A
100 - 64000min
0.00 - 10.00 (s)
0.0: Auto
0.1-25.0
0-100
Minimum setting
Default
value
value
(Panel/Comm.)
-
1
-
0
0.1/0.1
10.0
0.1/0.1
10.0
0.1/0.01
80.0
0.1/0.01
(*1)
0.1/0.01
0.0
-
(*1)
0.1/0.01
0.0
0.1/0.01
0.0
-
6
0.1/0.01
0.5
-
0
-
2
0.1/0.1
(*2)
0.01/0.01
(*2)
0.01/0.01
0.00
1/1
0
0.01/0.01
0.00
-
0
-
4
1/0.01
100
1/0.01
100
0.01/0.01
0.05
0.1/0.01
3.0
0.01/0.01
0.10
-
0
-
0
1/1
70
0.1/0.1
(*2)
0.01/0.01
(*2)
0.1/0.1
(*2)
-1
1/1
(*1)
0.01/0.01
0.00
-
0.0
-
35
16
E6581871
Setting
Notes
sample
0:Terminal input enabled
0
3:Setting dial 2
3
1.0
1.0
60.0
60.0
6.0
3: Vector control
3 (*3)
Operation frequency (Low)
10.0
Operation frequency (High)
60.0
68: Brake release signal (*3)
68
0.5
1:Enabled (Resistor overload
1
protection enabled)
1:Disabled
2 (*4)
2:Enabled (quick deceleration)
(*5)
(*6)
0.00
0
0
1
4
100
Refer to section 4.4.
60
0.05
3.0
0.10
1
Refer to of the VFS15
instruction manual
(*3)
(E6581611 :
section 6.1.5 or 625)
0.5(*7)
Setting is necessary at the
use of brake sequence
5.0
function.
Setting is necessary at the
use of brake sequence
20 (*8)
function.

Advertisement

Table of Contents
loading

Table of Contents