38 | Commissioning the heating system
7.6.2
Removing the blocking plate
You can remove the blocking plate to further raise the
flue gas temperature if the flue gas temperature is still
too low after removing of the baffles.
B Open burner door by removing the two hexagon bolts
at the sides.
B Remove blocking plate by loosening bolt.
B Re-check the flue gas temperature.
Fig. 58
Removing the blocking plate
7.7
Manual reset high limit (STB)
The manual reset high limit interrupts the power supply
if the maximum permissible flow temperature is
exceeded.
To enable a boiler reset and re-starting, the fault must be
removed and the system temperature must have fallen
below the limit.
B Check the function of the manual reset high limit
(
controls maintenance instructions).
6 720 648 162 (2011/08)
7.8
B Attach burner door jacket in the slots of the front
boiler cover.
B Slightly lift the burner door jacket until it hooks into
the bottom cross bar.
6 720 648 162-03.1T
Fig. 59
Installing jacket panels
DANGER: Risk of fatal injury from electric
shock.
B Only operate the boiler with the burner
hood/door panel fitted.
CAUTION: Risk of system damage from use
of incorrect fuel.
B Only use burners which meet the
technical requirements of the Bosch Uni
5000F (
Chapter 2.7, page 9).
Installing the burner door jacket
6 720 648 162-11.1T