Connecting
4.9 EMC guidelines
Grounding and high-frequency equipotential bonding measures
The following figure illustrates all grounding and high-frequency equipotential bonding
measures using an example with a SINAMICS G120P.
Figure 4-7
The ground connections
components. They are made with standard, heavy-power PE conductors without special
high-frequency properties and ensure low frequency equipotential bonding as well as
protection against injury.
The line supply cable of the inverter can be unshielded. The inverter has to be grounded by
this cable.
The shielded motor cable provides high-frequency equipotential bonding between the
inverter and the motor terminal box. The shield of the motor cable has to be connected to the
EMC shield busbar
On the motor side the shield has to be connected to the terminal box via an electrically
conductive PG gland
56
Grounding and high-frequency equipotential bonding measures in the drive system and
in the plant
represent the conventional grounding system for the drive
in the inverter by the integrated shield clips with a large contact area.
.
Hardware Installation Manual, 11/2014, A5E35319202B AA
PM230 Power Module IP55