General Data, Pm230, Ip55 - Siemens SINAMICS G120P Hardware Installation Manual

Power module pm230 ip55/ul type 12
Hide thumbs Also See for SINAMICS G120P:
Table of Contents

Advertisement

Technical specifications

6.1 General data, PM230, IP55

Definitions
• LO input current
• LO output current 100 % of the permissible output current with a load cycle according to
• LO power
• HO input current
• HO output current 100 % of the permissible output current with a load cycle according to
• HO power
6.1
General data, PM230, IP55
Feature
Line voltage
Output voltage
Input frequency
Output frequency
Power factor λ
Line impedance
Starting current
Pulse frequency (factory
setting)
Electromagnetic compatibil-
ity
Braking methods
Degree of protection
Operating temperature
Storage temperature
74
100 % of the permissible input current with a load cycle according to
Low Overload.
Low Overload.
Power of the Unit at LO output current.
100 % of the permissible input current with a load cycle according to
High Overload.
High Overload.
Power of the Unit at HO output current.
Version
380°V°...°480°V 3-ph.°AC ±°10%
0 V 3-ph. AC ... input voltage x 0.95 (max.)
50 Hz ... 60 Hz, ± 3 Hz
0 Hz ... 550 Hz, depending on the control mode
0.9
Uk ≤ 1%, no line reactor permitted
Less than the input current
4 kHz
The pulse frequency can be increased in 2 kHz steps up to 16 kHz (up to 8 kHz for 75 kW
and 90 kW). An increase in the pulse frequency results in a lower output current.
Conducted interference: The Power Modules correspond to Categories C1 and C2 of the
second environment according to IEC61800-3.
Radiated interference: The Power Modules comply with Category C2 of the second envi-
ronment according to IEC61800-3.
For details, see Electromagnetic Compatibility (Page 83)
DC braking
FSA ... FSC IP55 / UL Type 12
FSD ... FSF IP55 / UL Type 12 in preparation
Note: For the end cover plate, you must use the relevant bolting plates for the cable glands
and the corresponding cable glands and seals to achieve the degree of protection UP55 (UL
type 12).
Degree of protection IP54 / UL Type 12 is reached if an IOP is inserted.
for operation with LO base load pow-
er
for operation with HO base load
power
Derating see Temperature, altitude and voltage derating PM230 (Page 75)
-40 °C ... +70 °C
-10 °C ... +40 °C; with derating up to 60° C
-10 °C °... +50 °C; with derating up to 60° C
Hardware Installation Manual, 11/2014, A5E35319202B AA