Location
To prevent jamming of alarm and other
reports, wire and locate the RJ31X jack
so that normal phone use is temporarily
interrupted while the D9068 transmits
data (refer to Figure 15). After
installation, verify that the D9068
seizes the line, acquires the dial tone,
and reports correctly to the receiver.

Figure 15: RJ31X Wiring

6
1
2
3
4
5
6
7
5
8
1 - Full modular phone jack
2 - Ring (telco)
3 - Tip (telco)
4 - RJ31X Module
5 - T1 (house telephone tip)
6 - R1 (house telephone ring)
Use the supplied telco cable
assemblies to connect to an
RJ31X jack. Ensure that the
RJ31X jacks are mounted in a
secure location to prevent
unwanted disconnections or
tampering.
Notification
Do not connect registered equipment to
party lines or coin-operated telephones.
If the local telephone company requests
notification before you connect the
D9068 to the telephone network, tell
them:
Which line you are connecting to the
DACT.
The make, model, and serial number of
the device.
The FCC registration number
(ESVMUL-46514-AL-E) and ringer
equivalence (0.0B).
18
1
2
3
4
Bosch Security Systems, Inc. | 3/13 | F01U071094-07
If the telephone company changes its
communications facilities, equipment,
operations, or procedures that could
affect the performance of the D9068, the
telephone company is obligated to notify
the user in writing.
The D9068 meets the UL1950 requirements.
Connecting the Keypad to the D9068
The LCD Remote Keypad is used
strictly for programming and
debugging purposes.
Use the D7033/FMR-DACT-KEYPAD Keypad
Programmer to operate the D9068
Communicator. Remove the cover from the
D9068 case and connect the Molex
connector from the D7033/FMR-DACT-KEYPAD
to the connector pins located on the
D9068 board.
When programming the D9068 from the
keypad:
1. Set the D7033/FMR-DACT-KEYPAD address
between 1 and 15.
2. Use the wire connector supplied with
the D9068 to connect the keypad to
the D9068 (Figure 16 on page 19).