Wiring for Open-collector Output Terminals (Terminal No.8 to 10)
· When using open-collector output terminals to drive inductive loads, always connect
a freewheel diode.
Internal circuit of
the inverter
Wiring for analog signal terminals (Terminal No.11 to 14)
· When parameter P004 is set to "1", frequency setting will be made through external
potentiometer.
· When parameter P004 is set to "4" (4 to 20mA) or "5" (0 to 20mA), frequency setting
will be made through analog current signal.
· When the analog current signal is used, no resistor is required to be connected
between external terminals. (Resistor is built in.)
Wiring for RS485 communication terminals (Terminal No.16 to 18)
The following figure shows the terminals used when connection is made between PC
and PLC via RS485 communication lines.
D+
· Use the shielded twisted-pair cable as communication cable, and separate it from
power lines or high-voltage circuits (20cm or more).
· The total wiring length of the communication cables must not exceed 500m.
· Jump out the terminal "D-" and "E" of inverter used as terminal station. Jumping is
not allowed for any other device.
Terminal
⑧,⑨
Terminal ⑩
D-
D+
Freewheel diode
×
24V DC
power supply, etc.
Terminal station
D-
D+
D-
E
Jumping out
22