Panasonic AMK3000P22 Installation Manual page 45

Mk300 series. 1-phase 200v(0.2kw-2.2kw), 3-phase 400v(0.75kw-15kw)
Table of Contents

Advertisement

Function
No.
name
during RUN
Torque
P062
Boost
Amplitude
Torque
Boost
P063
Reply
Amplitude
Internal
component
cooling fan
P064
ON-OFF
control
selection
Changes
0 to 200
0 to 200
0: ON – when Run command is ON
OFF – when Run command is OFF
(FAn2 Trip Yes)
1: ON – when Run command is ON and internal
temperature is 40℃ or above
OFF – when Run command is OFF and internal
temperature is 30℃ or below (or power is turned
off)
(FAn2 Trip Yes)
2: ON – when Run command is ON
OFF – when Run command is OFF
(FAn2 Trip No/Alarm goes off)
3: ON – when Run command is ON and internal
temperature is 40℃ or above
OFF – when Run command is OFF or internal
temperature is 30℃ or below (or power is turned
off)
(FAn2 Trip No/Alarm goes off)
Setting range
Initial
Unit
value
1[%]
*4
1[%]
*4
3
44