Stationportal Device Driver - GE StationPortal User Manual

Production support device
Table of Contents

Advertisement

Option
Parameter
7
Keep-alive time
(seconds)
8
Gigabit Switch
L
Load last saved
configuration
S
Save and Exit
Q
Quit without Save

StationPortal Device Driver

A native CIMPLICITY device communication interface is available for the StationPortal. This
software can be ordered on CD as IC647NSD000.
GFK-2522A
Specifies the interval (in seconds) that StationPortal waits before
sending a keep-alive probe message across an idle TCP connection.
Note:
StationPortal will send keep-alive probe messages if there is
no activity on the network for the time period specified by
this parameter. If there is no response to its first keep-alive
probe message, StationPortal will send subsequent keep-
alive probe messages every 1 second. StationPortal will
send a maximum of eight keep-alive probe messages on an
idle network after which it will close its TCP ports.
Note:
A value of 0 indicates that keep-alive messages are
disabled. In such cases, StationPortal will not be able to
detect all communication losses. If communication loss isn't
properly detected, the client may be unable to reconnect to
StationPortal. Thus, we recommend that a non-zero value
be specified.
Specifies whether StationPortal is connected to a Gigabit Switch /
Controller or 10/100 Mbps switch / controller
Note:
When StationPortal is connected to a 10/100 Mbps switch /
controller or to a Gigabit switch with Auto-negotiation mode
disabled, this parameter should be set to "No". This
parameter should be set to "Yes" only when StationPortal is
connected to a Gigabit switch / controller with Auto-
negotiation mode enabled.
Reverts to the previously saved (using the "Save and Exit
command") configuration settings.
Note:
StationPortal maintains a copy of only the most recently
saved configuration that is used for current operation. As a
result, this option cannot be used to revert to an earlier
configuration.
Save the changes made to the configuration settings as the current
operational settings and exits the Configuration Menu.
Exits the configuration menu without saving changes made to the
configuration settings.
Description
Hardware Configuration
Format
0 to 65535
0=No
1=Yes
"L" or 'l' (lower-
case L)
"S" or "s"
"Q" or "q"
15

Advertisement

Table of Contents
loading

Table of Contents