ABB COM600 series User's & Technical Manual page 15

5.1 substation analytics
Hide thumbs Also See for COM600 series:
Table of Contents

Advertisement

1MRS758734
COM600 series 5.1
Substation Analytics Technical Manual
provides the correct result for a specific fault type. A three-phase fault is an exception
and theoretically it can be calculated with any of the fault loops. The fault loop used in
the fault distance calculation is indicated in the monitored data FAULT_LOOP as spe-
cified in Table 4.3-1.
Table 4.3-1 Fault types and corresponding fault loops
Fault Type
A-E
B-E
C-E
A-B
B-C
C-A
A-B-C-(E)
In case of phase-to-phase-to-earth-faults (A-B-E, B-C-E or C-A-E), the selected fault
loop depends on the location of the individual earth faults. When the faults are located
at the same feeder, the corresponding phase-to-phase loop (either "AB Fault" or "BC
Fault" or "CA Fault") is used for calculation. When the faults are located at different
feeders, the phase-to-earth loop (either "AG Fault" or "BG Fault" or "CG Fault") corres-
ponding to the faulty phase at the protected feeder is used for calculation.
Identification of the faulty phase is provided by the built-in Phase Selection Logic (PSL),
based on combined impedance and current criteria. Phase selection logic is virtually
setting-free and has only one parameter, Z Max phase load, for discriminating a large
symmetrical load from a three-phase fault. The parameter Z Max phase load can be cal-
culated using the equation:
Figure 4.3-2 (Equation 1)
Uxy: the nominal phase-to-phase voltage
S
the maximum three-phase load
max
For example, if Uxy = 20 kV and S
Fault distance calculation
As soon as a fault condition is recognized by the phase selection logic, the fault distance
calculation is started with one of the seven impedance-measuring elements, that is, the
Description
Phase A-to-earth fault
Phase B-to-earth fault
Phase C-to-earth fault
Phase A-to-B short circuit fault
Phase B-to-C short circuit fault
Phase C-to-S short circuit fault
Three-phase short circuit
= 1 MVA, then Z Max phase load = 320.0 ohm.
max
Output FAULT_LOOP
1
2
3
4
5
6
7
equation_1.png
15

Advertisement

Table of Contents
loading

Table of Contents