3.3.4.
3.3.5.
3.3.6.
3.3.7.
3.3.8.
12
COM600 series 5.1
Substation Analytics Technical Manual
Periodic triggering is used to ensure the accuracy of charge time calculation.
Gas Pressure Trigger Application
Gas pressure trigger application listens to data changes of trigger data points coming
from the IED. Trigger condition are based on status changes of the gas pressure signal.
This will then trigger the execution of gas pressure main application.
Circuit Breaker Condition Monitoring Main Application
The circuit breaker condition monitoring main application calculates circuit breaker
condition monitoring data according to the inputs from the IED. Without comtrade data
for the triggering time it will produce circuit breaker trip time, circuit breaker inactivity
and operations count calculations. If comtrade data is available it will additionally produce
circuit breaker accumulated energy data and circuit breaker trip time calculation is pro-
duced with better accuracy.
Spring Charge Main Application
Spring charge main application calculates the spring charge time and activates alarm out
according to input and setting values.
Gas Pressure Main Application
Gas pressure main application activates alarm out according to input and setting values.
IEC 61850 Main Application
The IEC 61850 main application contains mappings to the OffSide OPC server. This is
a crucial part of piping the results onwards from the analytics. The application is run
whenever any of the main applications are reporting new results.
1MRS758734