Advertisement

5.11.
56
COM600 series 5.1
Substation Analytics Technical Manual
Name
Type
CBAccEnePhsB
DOUBLE
CBAccEnePhsC
DOUBLE
SprChrTm
DOUBLE
CbOprCnt
INT
InActDays
INT

Settings

Table 5.11-1 SSCBR settings
Parameter
Values (Range)
TripledZeroSeq
TRUE
FALSE
GroupDelay
SamplingFre-
quency
Gas Pressure
0....60
Alarm Time
Gas Pressure
0....60
Lockout Time
Initial Value for
0....25000
Accumulated
Energy
Operation Coeffi-
-3....-0.5
cient
Rated Operating
0....10000
Current
Rated Fault Cur-
0....30000
rent
Number of Opera-
0....10000
tions for Rated
Current
Number of Opera-
0....10000
tions for Rated
Fault Current
Current Factor 'y'
1....2
Default
0 = false
0 = false
0 = false
0
0
Unit
Step
Default
False
ms
1
0
Hz
1
1600
S
1
0.1
S
1
0.1
Energy
1
0
Coeff
0.5
-1.5
A
1
1000
A
1
10000
Count
1
10000
Count
1
1000
Power
1
1
factor
1MRS758734
Description
Phase B accumulated
energy
Phase C accumulated
energy
Spring charging time
Number of CB opera-
tions
Inactive days
Description
If set to false then the zero
sequence calculated by
symCom_A is divided by 3
Group delay for samples of
the input signal [ms].
Sampling frequency of the
input signal [Hz]
Time delay to delay the
pressure alarm (s)
Time delay to delay the
pressure lockout (s)
Initial accumulated energy
()
Directional coefficient
Rated operation current
Rated fault current
Operations number rated
Operations number fault
Current power factor