A B B M E A S U R E M E N T & A N A L Y T I C S | O P E R A T I N G I N S T R U C T I O N Pressure transmitter Models 261GS/GC/GG/GJ/GM/GN/GR Models 261AS/AC/AG/AJ/AM/AN/AR Measurement made easy —...
Change from one to two columns Contents Configuration, parameterization ........24 7.1.1 Standard configuration ........24 Safety ................5 Configuration types ..........24 General information and notes for the reader ..5 ...
Safety Improper use The following are considered to be instances of improper use of the device: General information and notes for the reader — For operating as a flexible adapter in piping, e.g. for These instructions are an important part of the product and compensating pipe offsets, pipe vibrations, pipe must be retained for future reference.
Name plate Plates and symbols 1.6.1 Safety / warning symbols, note symbols The warnings in these instructions are structured as follows: DANGER The signal word "DANGER" indicates an imminent danger. Failure to observe this information will result in death or severe injury.
The CE marking on the device does not refer to the Pressure must observe the following regulations for shipping purposes: Equipment Directive. All devices delivered to ABB must be free from any hazardous The name plate then contains the following identification materials (acids, alkalis, solvents, etc.).
This includes the environmentally-friendly use of natural — If it is not possible to dispose of old equipment properly, resources. We conduct an open dialog with the public through ABB Service can take receipt of and dispose of returns for our publications. a fee.
The EC type examination certificates to be communication / configuration / parameterization in a applied are available for download online on the ABB website. potentially explosive atmosphere with type of protection "intrinsic safety", the devices used must be certified Type of protection "intrinsic safety Ex i"...
Function and system design Operation and system setup The transmitter has a compact design and comprises the pressure measuring cell and electronic unit with pushbutton Digital pressure transmitters are communication-ready field control. Depending on the measuring range and measured devices with microprocessor-controlled electronics. variable, a silicon pressure sensor is used.
Page 11
To measure the output signal and configure / calibrate the pressure transmitter, an ampere meter must be connected directly to the output circuit. The lower and upper range values can be set via a pushbutton on the electronic unit. An optional fastener is available for attaching a stainless steel tag so that the measuring points can be indicated.
Mounting Pressure transmitter The pressure transmitter can be connected directly to the shut-off valve. An angle bracket for wall or pipe mounting (2" Before installing the transmitter, check whether the device pipe) is also available as an accessory. design meets the requirements of the measuring point from a The pressure transmitter should be installed so that the measurement technology and safety specifications point of display and control unit are accessible during installation and...
Sealing and screw connections Moisture Connecting G ½ B spigot: Use suitable cables and tighten cable glands securely. The For sealing, a flat gasket must be used in accordance with DIN transmitter can also be protected against the ingress of EN 837-1.
Measuring pipe In order for the pipes to be laid correctly, the following points must be observed: — Keep the measuring pipe as short as possible and avoid sharp bends. — Lay the measuring pipe in such a way that no deposits can accumulate in it.
Electrical connections Cable connection Depending on the model supplied, the electrical connection is established via cable gland M16x1.5 (for diameters of WARNING – Electrical dangers! 5 to 10 mm) or M20x1.5 (for diameters of 6 to 11 mm), a Observe the applicable regulations governing threaded bore for cable gland 1/2-14 NPT, or via the Han 8U electrical installation.
Change from two to one column Electrical connection in the cable connection area Fig. 7 1 Pushbutton for lower/upper range values | 2 + Signal screw terminals for leads with cross-section of 0.5 … 1.5 mm 3 - Signal screw terminals for leads with a cross-section of 0.5 … 1.5 mm | 4 Grounding / equipotential bonding terminal (optional) | 5 Cable entry | 6 Line load | 7 Grounding | 8 Handheld terminal | 9 Resistor (min.
If this value is not achieved within the context of normal installation, an additional resistor must be used. The ABB Contrans I supply modules with HART communication already have a factory-installed, additional resistor. Some of these modules offer the option of Fig.
Change from two to one column – – I + FSK 2600T RS 232C M10693 Fig. 11: "Point-to-point" communication mode 1 Pressure transmitter | 2 Possible connecting points for a modem between A and B | 3 Power supply unit | 4 FSK modem 4 &...
Commissioning Output signal If the applied pressure is within the values indicated on the name plate, the output current ranges between 4 und 20 mA. General remarks If the pressure applied falls outside the set range, the output Once the pressure transmitter has been installed, it is put into current will be between 3.5 mA and 4 mA if the range is operation by switching on the operating voltage.
Adjusting lower range value / oblique sensor Correction procedure "A" described above does not affect the physical pressure shown; it only corrects the analog output During installation of the transmitter, zero position shifts may signal. For this reason, the analog output signal may differ occur due to the mounting position;...
Installing/Removing the LCD indicator 3. No tools are required to insert the LCD indicator. Carefully insert both guide pins for the LCD indicator in the guide holes of the transmitter inset. Make sure the black connection socket fits into the terminal on the transmitter inset.
Pressure sensor ventilation M10695 Fig. 15: Ventilation unit For technical reasons, you must apply atmospheric pressure to the reference side of the pressure sensor. A special ventilation unit (1) is screwed into the electronic housing from the outside and is equipped with a PTFE filter on the inside.
Configuration, parameterization Configuration using pushbutton on pressure transmitter 7.3.1 General remarks NOTICE – Potential damage to device as a The pushbutton is located on the electronics unit (without result of electrostatic charging! mounted LCD indicator). When the housing is open, EMC protection is The pushbutton is used to set the "Lower Range Value"...
Any potential measuring error for the pressure generator Configuration with the LCD indicator should be at least three times smaller than the desired measuring error for the transmitter. IMPORTANT (NOTICE) It is recommended that, if time constant is known, you set the To access the control buttons for the LCD damping to zero (via LCD indicator or graphical user interface).
7.4.2 Process display Error messages on the LCD display In the event of an error, a flashing message consisting of an icon and text (e.g., device defective) appears at the bottom of the process display. If you press the left LCD indicator button while a message is flashing, the text becomes permanent.
Change from two to one column 7.4.4 Menu structure The parameters are structured in the form of a menu. The menu consists of a maximum of three levels. Menu items with an asterisk (*) have additional parameters that are described in the next section. main menu Submenu 1 Submenu 2...
7.4.5 Parameter descriptions Offset Enabling / disabling (Write Protect) Via LCD indicator, DTM or handheld terminal. If “Write Protect” is enabled, it is not possible to configure the 261G/A pressure transmitter. All editing functions on the indicator are hidden, except for write protection. It is, however, possible to read out data.
Page 29
Damping Installation angle When the output signal for the transmitter is noisy as a result You can specify the extent to which the transmitter deviates of the process, the signal can be smoothed (damped) from the recommended nominal position (vertical, process electrically.
Page 30
Diagnosis The parameters listed can be displayed temporarily in this view (not failsafe memory). The value configured under “Main operator view” remains unchanged. IMPORTANT (NOTICE) The LCD indicator automatically returns to the process display approximately three minutes after the last button was pressed. HART Tag Each transmitter requires a unique bus ID in order to communicate within a bus structure.
Configuration with the graphical user interface (DTM) Parameter descriptions 7.5.1 System requirements Write protection — Operating control program (e.g. SMART VISION version Enabling/Disabling is performed via the DTM, handheld 4.01 or higher) terminal or LCD indicator. — DTM or Asset Vision Basic (Device Type Manager, graphic When “Write Protect”...
Page 32
Setting the “Lower Range Value” and “Upper Range Offset Value” Menu path: Menu path: “Configure_Configure Pressure Measurement_Pressure” “Configure_Configure Pressure Measurement_Pressure” This function performs a parallel shift of the characteristic The “Scaling” field offers two setting options. curve so that it travels through a point specified by the user. This makes it possible to set the output signal of several 1.
min. 250 Ω Configuration with the PC / laptop or handheld terminal A graphical user interface (DTM) is required for configuration of – – the transmitter via PC or laptop. For operating instructions, I + FSK please refer to the software description. Further information: Data sheet on DTM / SMART VISION or ASSET VISION BASIC Communications protocol:...
Configuration with the graphical user interface (DTM) Parameter descriptions 7.8.1 System requirements Write protection — Operating control program (e.g. SMART VISION version Enabling/Disabling is performed via the DTM, handheld 4.01 or higher) terminal or LCD indicator. — DTM or Asset Vision Basic (Device Type Manager, graphic When “Write Protect”...
Page 35
Setting the “Lower Range Value” and “Upper Range Offset Value” Menu path: Menu path: “Configure_Configure Pressure Measurement_Pressure” “Configure_Configure Pressure Measurement_Pressure” This function performs a parallel shift of the characteristic The “Scaling” field offers two setting options. curve so that it travels through a point specified by the user. This makes it possible to set the output signal of several 1.
Ex relevant specifications 8.1.2 IECEx transmitter with the following types of protection: ‘Intrinsic Safety ia’, ‘non sparking nA’ and ‘dust ignition protection by enclosure tb’ Hazardous atmospheres 8.1.1 ATEX transmitter with ‘intrinsic safety Ex ia/ib’ type Transmitter with 4 ... 20 mA output signal and HART communication of protection in accordance with Directive Certificate no.
8.1.3 Factory Mutual (FM) Transmitter with 4 ... 20 mA output signal and HART communication Intrinsic Safety Class I; II and III; Division 1; Groups A, B, C, D; E, F, G Class I; Zone 0; AEx ia Group IIC T6; T4 Non-incendive Class I, II, III, Division 2;...
9.2.2 Temperature limits °C (°F) Shock resistance Environment Acceleration: 50 g Duration: 11 ms Model 261GS, 261AS Ambient temperature limits (according to 60068-2-27) Operating temperature range -40 … 85 °C (-40 … 185 °F) White oil filling -6 to 85 °C (21 to 185 °F)
Measuring accuracy 9.3.5 Temperature coefficient (T 9.3.1 Reference conditions according to IEC 60770 Effect of the ambient temperature per 10 K (but limited to the — Ambient temperature TU = constant in the range maximum effect of the temperature change, see previous 18 ...
9.4.2 Calibration 9.3.12 Total performance Standard: Similar to DIN 16086 — 0 to upper range limit (URL) In the range -10 … 60 °C (14 … 140 °F): Optional: 0.42% of the set span (TD 1:1) — To specified measuring span The total performance accuracy includes the measuring error (non-linearity including hysteresis and non-reproducibility), as 9.4.3...
9.5.2 Version with the options “LCD indicator” and “Harting Han plug” Ø 60 (2.36) 102 (4.02) Ø 21 (0.83) Ø 28 (2.13) M10685-01 Fig. 25: Dimensions — with options 1 Housing cover for LCD indicator option Dimensions for sensor code C, F Dimension "A"...
9.5.3 Transmitter with flush diaphragm Fig. 26: Dimensions - With flush diaphragm 1 Welded connections / tapped hole for flush diaphragm, part no. 284903 | 2 No burrs | 3 Groove for gasket DIN 3869 - 21 18.5 x 23.9 x 1.5 | 4 Groove for O-ring 15 x 2 Bevel after cutting threads Minimum dimension Wrench size 27...
9.5.5 Mounting with angle bracket (optional) 12,5 (0.49) (0.59) 72 (2.83) 72 (2.83) (0.79) M10688-01 Fig. 28: Dimensions — pipe mounting/wall mounting 1) Dimensions for sensor code C, F 2) Sensor code L, D, U, 1, R, V IMPORTANT (NOTICE) The bracket for wall or pipe mounting has four holes with a Ø...
10 Maintenance / Repair 10.1 Removal WARNING – Potential danger if device is WARNING disassembled incorrectly! Bodily injury! Before removing or disassembling the device, The device can be operated at high pressure and with check for hazardous process conditions such as aggressive media.
Designation relating to intended use in potentially explosive atmospheres in compliance with: protection — ATEX Directive (additional identification with CE mark) NOTICE All documentation, declarations of conformity, and certificates are available in ABB's download area. www.abb.com/pressure 261Gx, 261Ax | IM/261Gx/Ax-EN Rev. 08 49...
Page 50
Statement on the contamination of devices and components Repair and / or maintenance work will only be performed on devices and components if a statement form has been completed and submitted. Otherwise, the device / component returned may be rejected. This statement form may only be completed and signed by authorized specialist personnel employed by the operator.
Page 52
We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. ABB does not accept any responsibility whatsoever for potential errors or possible lack of information in this document.