High Efficiency Function Operation (Auto Dust Throw Mode) (Fn11) - LG Multi V5 Service Manual

Hide thumbs Also See for Multi V5:
Table of Contents

Advertisement

High Efficiency Function Operation
(Auto Dust Throw Mode) (Fn11)
High Efficiency Function (Auto Dust Throw Mode) helps remove
dirt / sand / debris that could have collected on the outdoor unit coil
surface. After the cooling, heating, etc., mode is satisfied and the
compressors are idle, this function will start the fan motors, operat-
ing them at full speed and in the reverse direction for a certain pe-
riod. Air is drawn in through the top of the outdoor unit, and passes
through the coil to help dislodge any loose debris.
The Auto Dust Option oP3 allows the Auto Dust Throw Mode to be
called through a third-party signal at any time. When the oP3 setting
is used, an LG I / O Module (sold separately) MUST be installed.
When the signal is sent to the outdoor unit via a third party source
(oP3), normal system operation can be interrupted, and the Auto
Dust Throw function can be performed. All other settings will not
interrupt the Multi V system operation.
Use on both heat pump and heat recovery systems.
The Auto Dust Mode function is not a substitute for coil cleaning and does not clear the coil of all debris. A coil cleaning procedure must be included
when performing regular preventative maintenance.
Table 32:
Settings
oFF (Default)
oP1
oP2
oP3*
oP4
oP5
*op3 requires LG's I / O Module (sold separately).
Reverse Cycle Fan
Runtime (Minutes)
-
5
5
3
1
1
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
OTHER CONTROLS
Figure 21:
Turn No. 5 on the master outdoor unit PCB
DIP switch bank SW01 to ON.
Select from "oFF", "oP1" through "oP5" options (see table) options by
The High Efficiency Function (Auto Dust Throw) is set. PCB does not
Time Delay Between Cycles
-
2 Hours
2 Hours
5 Minutes Following
Compressor Shutdown
-
1 Hour
Setting Optional Modes
need reset.
Number of Cycles
-
No Limit
2
1
1
2
71