ABB LME620-AI User Manual page 26

Electronic unit for field installation for the control of contrac control actuators series pme, lme, rhd and rsd
Hide thumbs Also See for LME620-AI:
Table of Contents

Advertisement

26
LME620-AI / PME120-AI / EAN823 / EBN853 / EBN861 ELECTRONIC UNIT | OI/PME/LME/EAN823/EBN853/EBN861-EN REV. E
... 6 Electrical connections
... Electrical data for inputs and outputs
EBN861
Supply voltage (standard actuators)
Supply voltage (Ex actuators)
Current consumption at the electronic unit
(AC 230 V)
External fuse for electronic unit
Binary inputs and outputs - communication
Conventional communication
Analog input
Analog output
3 digital inputs, 1 to 3
3 digital outputs, 1 to 3
Digital communication
Default settings
Voltage output U
V
Connection for transmitter (optional)
Individual settings
230 V AC (190 to 260 V); 47.5 63 Hz; single-phase
230 V AC (190 to 253 V); 47.5 63 Hz; single-phase
Actuator
l
at 230 V
max
RHD(E)2500-10
5.3 A
RHD(E)4000-10
10.0 A
RHD8000-12
8.0 A
RHDE8000-15
8.0 A
RHD(E)16000-30
12.5 A
RSD(E)50-10
6.4 A
RSD100-10.0
12.5 A
RSD200-5.0
13.0 A
Safety fuse 35 A (Lindner) + thermal circuit breaker 16 A (ETA); fuses are in the scope of delivery
0 / 4 to 20 mA, internal load: 300 Ω
0 / 4 to 20 mA, electrically isolated, maximum load: 500 Ω
Digital 0: −3 to 5 V or open, electrically isolated
Digital 1: 12 to 35 V, electrically isolated
Potential-free relay contact, max. 60 V, 150 mA
RS232 for commissioning and service, optionally FSK / HART®
Conventional communication on page 11
24 V, 15 mA, electrically isolated, for scanning external contacts, or similar applications
Supply for two-wire transmitter with activated process controller in Contrac
See data sheet 'DS/CONTRAC/SETTING' or available upon request.
l
(230 V): approx. 40 to 50 % of l
pos
max