Installation
WARNINGS:
• SITRANS Probe LU is to be used only in the manner outlined in this
manual, otherwise protection provided by the equipment may be
impaired.
• Installation shall only be performed by qualified personnel and in
accordance with local governing regulations.
Notes:
•
Refer to the device nameplate for information on approvals.
•
This product is susceptible to electrostatic shock. Follow proper grounding
procedures.
•
Ideally, mount SITRANS Probe LU so that the face of the transducer is at least 300
mm (1 ft) above the highest anticipated level.
Mounting Location
Recommendations:
•
Ambient temperature within –40 to 80
•
Easy access for viewing the display and programming via the handheld programmer.
•
An environment suitable to the housing rating and materials of construction.
•
Keep the sound path perpendicular to the material surface.
.
ambient temperature
surrounding enclosure
o
–40 to 80
C (–40 to 176
process temperature
o
–40 to 85
C (–40 to 185
A5E32337695
SITRANS Probe LU (HART) – OPERATING INSTRUCTIONS
o
F)
o
F)
o
o
C (–40 to 176
F).
flange adaptor (option)
customer-supplied
flange
Page 11