Appendix G: Hazardous Area Installations; Wiring Details; Intrinsically Safe Model - Siemens SITRANS Probe LU Operating Instructions Manual

Ultraschall transmitter
Hide thumbs Also See for SITRANS Probe LU:
Table of Contents

Advertisement

Appendix G: Hazardous area
installations

Wiring details

Instructions specific to hazardous area installations
Wiring Details

Intrinsically Safe Model

FM
(reference drawing 23650516: see page 99)
CSA
(reference drawing 23650517: see page 100)
Under the entity evaluation concept, SITRANS Probe LU has the following
characteristics:
(input voltage) U
(input current) I
(input power) P
Definition:
The Entity Concept allows interconnection of intrinsically safe apparatus to associated
apparatus not specifically examined in such combination. The criteria for interconnection
is that the voltage and current which intrinsically safe apparatus can receive and remain
intrinsically safe, considering faults, must be equal to or greater than the output voltage
(U
) and output current (I
o
considering faults and applicable factors. In addition, the maximum unprotected
capacitance (Ci) and Inductance (Li) of the intrinsically safe apparatus, including
interconnecting wiring, must be equal to or less than the capacitance and inductance
which can be safely connected to associated apparatus.
A5E32337695
SITRANS Probe LU (HART) – OPERATING INSTRUCTIONS
= 30 V DC (max.)
i
= 120 mA DC (max.)
i
= 0.8 W
i
) levels which can be delivered by the associated apparatus,
o
Page 93

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents