Ma Output (P201 To P215) - Siemens SITRANS Probe LU Operating Instructions Manual

Ultraschall transmitter
Hide thumbs Also See for SITRANS Probe LU:
Table of Contents

Advertisement

P073 Failsafe level
Defines a user-defined level to report when the Failsafe timer expires.
Values
P071 must be set to User-selected value (4) to use this value.
Note:

mA Output (P201 to P215)

P201 mA Output Function
Alters the mA output/measurement relationship, and allows the output to be set
independently from P001. If a HART master is connected, only the master can change the
value.
0
1
2
Values
3
4
Notes:
• P201 is set independently from P001: set P001 first, as changing P001 will reset P201
to the same setting.
• P201 controls the primary value and the loop current for the HART common module
and should not be changed if using HART.
• Selection also affects the secondary, tertiary, and quaternary variables for HART.
• P201 must be set to 0 (manual) before you can modify P911. Remember to restore the
previous setting after using P911.
Independent mA Setpoint Parameters (P210 and P211)
P210 and P211 allow you to explicitly define the normal operating range. Use these
features to reference the minimum and/or maximum mA output to any point in the
measurement range.
For HART, 4 mA and 20 mA represent the upper and lower range limits for the primary
variable.
A5E32337695
SITRANS Probe LU (HART) – OPERATING INSTRUCTIONS
Range
Default
manual
*
level
space
distance
volume (only available if a tank shape has been selected at P050)
or flow (only available if 9 is selected at P050, and head level and flow
breakpoints are set at P054 and P055)
3.6000 mA to 22.600 mA
22.600 mA
Page 43