Siemens CRM-4 Installation Instructions
Siemens CRM-4 Installation Instructions

Siemens CRM-4 Installation Instructions

Controllable relay module

Advertisement

Quick Links

Installation Instructions
Model CRM-4
Controllable Relay Module
The Model CRM-4 Controllable Relay Module
from Siemens Industry, Inc. provides auxiliary
control of building functions such as door holder
release, elevator capture, smoke control, lock
release, etc.
OPERATION
Each CRM-4 module provides four fully program-
mable relays. Each relay contains one set of
SPDT contacts rated at 2A, 30 VDC/120 VAC
resistive. All relay coils are supervised in a de-
energized state to provide proper operation.
Individual relays can be automatically activated
or deactivated through control by event and time
based logic contained in the MXL. Each relay
Siemens Industry, Inc.
Building Technologies Division
Florham Park, NJ
P/N 315-090853-7
may also be either manually controlled or may
be disarmed through the MXL keypad. When
any relay is disarmed, the LCD annunciator
indicates the affected relay, and the PARTIAL
SYSTEM DISABLE and TROUBLE indicators
light until the relay is returned to an armed
condition.
Four LEDs are provided on the CRM-4. Two
diagnostic LEDs provide positive indication of
the CRM-4's network communication. The
other two are user programmable through the
MXL software.
For additional information, refer to the
MXL/MXLV Manual, P/N 315-092036.
Figure 1
MOM-4 Slots for the CRM-4
Siemens Building Technologies, Ltd.
Fire Safety & Security Products
2 Kenview Boulevard
Brampton, Ontario
L6T 5E4 Canada

Advertisement

loading

Summary of Contents for Siemens CRM-4

  • Page 1 OPERATION condition. Four LEDs are provided on the CRM-4. Two Each CRM-4 module provides four fully program- diagnostic LEDs provide positive indication of mable relays. Each relay contains one set of the CRM-4’s network communication.
  • Page 2 MOM-4 Expansion module. There are four avail- Mounting the CRM-4 able slots for the CRM-4 on the MOM-4 (See The CRM-4 module has a card guide that must be Figure 1). Selecting which position on the MOM-4 installed into the MOM-4 (See Figure 4). To install...
  • Page 3 NOTE: RELAYS K1 - K4 ARE PROGRAMMABLE. Figure 3 CRM-4 Relay Wiring Figure 4 Installing a Card Guide...
  • Page 4 TABLE 1 NETWORK ADDRESS PROGRAMMING 8 76 5 43 21 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 8 7 6 5 4 3 2 1 ADDR ADDR ADDR ADDR ILLEGAL OXOOOOOO XOOOOOOO XXOOOOOO ILLEGAL...