Siemens SIPROTEC 7SJ80 Manual

Siemens SIPROTEC 7SJ80 Manual

Overcurrent protection, motor protection, voltage and frequency protection
Hide thumbs Also See for SIPROTEC 7SJ80:

Advertisement

SIPROTEC
7SJ80
Motor Protection
7SK80
Voltage and Frequency
Protection
7RW80
Communication module
DNP 3.0
Bus mapping / Point lists
Edition: September 2010
C53000-L2040-A320-2
Preface
Table of Contents
1
2
3

Advertisement

Table of Contents
loading

Summary of Contents for Siemens SIPROTEC 7SJ80

  • Page 1 Preface Table of Contents Notes to SIPROTEC objects SIPROTEC DNP V3.0 Device Profile Overcurrent Protection Point lists 7SJ80 Glossary Motor Protection 7SK80 Index Voltage and Frequency Protection 7RW80 Communication module DNP 3.0 Bus mapping / Point lists Edition: September 2010 C53000-L2040-A320-2...
  • Page 2 We reserve the right to make technical improvements with- SIPROTEC, SINAUT, SICAM, and DIGSI are registered trade- out notice. marks of SIEMENS AG. Other names and terms can be trade- V01.10.01 marks the use of which may violate the rights of thirds.
  • Page 3 SIPROTEC devices: Manual Contents Order number Overcurrent Protection Function, operation, assembly and commissioning E50417-G1140-C343 SIPROTEC 7SJ80 of the SIPROTEC device 7SJ80 V4.6 Motor Protection Function, operation, assembly and commissioning E50417-G1140-C344 SIPROTEC 7SK80 of the SIPROTEC device 7SK80 V4.6...
  • Page 4 Siemens representative. Individual course offerings may be found in our Training Catalogue, or questions may Training Courses be directed to our training center. Please contact your Siemens representative. SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2...
  • Page 5 Preface The warnings and notes contained in this manual serve for your own safety and for an Instructions and appropriate lifetime of the device. Please observe them! Warnings The following terms are used: DANGER indicates that death, severe personal injury or substantial property damage will result if proper precautions are not taken.
  • Page 6 Preface The following text formats are used when literal information from the device or to the Typographic and device appear in the text flow: Symbol Conven- tions Parameter names, i.e. designators of configuration or function parameters which may appear word-for-word in the display of the device or on the screen of a personal computer (with operation software DIGSI 4), are marked in bold letters of a mono- space type style.
  • Page 7 Table of Contents Table of Contents Preface..............................3 Table of Contents ..........................7 Notes to SIPROTEC objects ....................... 9 Binary Inputs / Annunciations ....................10 1.1.1 Error with a summary alarm ....................10 1.1.2 Alarm Summary Event......................10 1.1.3 Stop Data Transmission ....................... 11 Binary Outputs / Commands ....................
  • Page 8 Table of Contents Binary Input Points........................ 25 3.2.1 Auto-Reclose Function ......................25 3.2.2 Overcurrent Protection......................25 3.2.3 InRush Function........................25 3.2.4 Directional Overcurrent Protection..................25 3.2.5 Negative Sequence Protection ..................... 26 3.2.6 Over/Underfrequency Protection ..................26 3.2.7 Under/Overvoltage Protection ....................26 3.2.8 (sensitive) Ground Fault Protection ..................
  • Page 9 Notes to SIPROTEC objects This chapter contains notes for the use and evaluation of certain SIPROTEC objects which are available via DNP3.0 communication. Binary Inputs / Annunciations Binary Outputs / Commands Analog Inputs / Measured values Metered measurands SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2...
  • Page 10 Notes to SIPROTEC objects Note The description of the standard mappings / point lists (ref. to chap. 3) contains the pre- allocation of the mapping files at delivery or first assignment of a mapping in DIGSI 4 to the SIPROTEC device. Changes of the allocation and the scaling of the measured values are possible in ad- aptation to the concrete installation enviroment (ref.
  • Page 11 Binary Outputs / Commands 1.1.3 Stop Data Transmission The functionality "Stop data transmission" is not supported via DNP communication. If "Stop data transmission" is active nevertheless data via DNP will be transmitted fur- thermore. The annunciation "DataStop" signals the activation of "Stop data transmission" how- ever and can be evaluated correspondingly in the DNP master.
  • Page 12 Notes to SIPROTEC objects ref. to chap. 3.3.2 Reference 1.2.3 Changing the setting group Switching on one setting group automatically switches off the current active setting group. Transmission of the value OFF is insignificant for the change of the setting group and is refused by the device.
  • Page 13 Metered measurands Metered measurands The scaling of the metered measurands, which are derived from measured values, re- Scaling fers to: 60000 impulses per hour for V = Vprim and I = Iprim = Full Scale Voltage prim (parameter address = 1101) CALE URRENT prim...
  • Page 14 Notes to SIPROTEC objects SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2...
  • Page 15 DNP V3.0 Device Profile Implementation Table Device Profile Document SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2...
  • Page 16 DNP V3.0 Device Profile Implementation Table The following table gives a list of all objects recognized and returned by the SIPRO- TEC device. For static objects, requests sent with qualifiers 00, 01, 06, 07 or 08 will be responded with qualifiers 00 or 01. Requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or 28.
  • Page 17 Implementation Table OBJECTS REQUEST RESPONSE Object Vari- Description Function Codes Qualifier Codes Function Codes Qualifier Codes ation (dec) (hex) (dec) (hex) 16-Bit Analog Input - 00, 01 (read) (start-stop) (no range) Any Variations 07, 08 (limited qfy) 17, 28 (index) 32-Bit Analog Input with Status 00, 01 00, 01...
  • Page 18 DNP V3.0 Device Profile Device Profile Document DNP V3.0 DEVICE PROFILE DOCUMENT Vendor Name: SIEMENS AG Device Name: 7SJ80/7SK80/7RW80 Highest DNP Level Supported: Device Function: For Requests DNP-L2 Master Slave For Responses DNP-L2 Notable objects, functions, and/or qualifiers supported in addition to the Highest DNP Levels Supported (the...
  • Page 19 Device Profile Document Requires Application Layer Confirmation: Never Always (not recommended) When reporting Event Data (Slave devices only) When sending multi-fragment responses (Slave devices only) Sometimes If 'Sometimes', when? ___________________________________ Configurable If 'Configurable', how? by the protection data processing program DIGSI 4 Timeouts while waiting for: Data Link Confirm None...
  • Page 20 DNP V3.0 Device Profile Reports Binary Input Change Events when no spe- Reports time-tagged Binary Input Change Events when cific variation requested: no specific variation requested: Never Never Only time-tagged Binary Input Change With Time Only non-time-tagged Binary Input Change With Relative Time Configurable to send both, one or the Configurable (attach explanation) other (attach explanation)
  • Page 21 Point lists Functional Scope Binary Input Points Control Relay Output Blocks/Binary Output Status Counters Analog Inputs SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2...
  • Page 22 Point lists Functional Scope Depending of the functional scope, some of the following described functions, annun- ciations, commands, measured and metered values are not available. 7SJ80 Table 3-1 7SJ80 Functional scope Function Ref. to Chapter Setting Group Change Option 3.2.14 Oscillographic Fault Records 50/51 (Charac.
  • Page 23 Functional Scope 7SK80 Table 3-2 7SK80 Functional scope Function Ref. to Chapter Setting Group Change Option 3.2.14 Oscillographic Fault Records 50/51 (Charac. Phase) Overcurrent Protection 3.2.2 50N/51N (Charac. Ground) Overcurrent Protection 3.2.2 67N, 67N-TOC Directional Overcurrent Protection 3.2.4 Cold Load Pickup 3.3.2 2nd Harmonic Inrush Restraint 3.2.3...
  • Page 24 Point lists 7RW80 Table 3-3 7RW80 Functional scope Function Ref. to Chapter Setting Group Change Option 3.2.14 Oscillographic Fault Records 24 Overexcitation Protection Jump of Voltage Vector 27, 59 Under/Overvoltage Protection 3.2.7 VT Broken wire supervision 81 Over/Underfrequency Protection 3.2.6 Load Restoration 25 Function group 1 Synchronism and Voltage Check 74TC Trip Circuit Supervision...
  • Page 25 Binary Input Points Binary Input Points Binary Input Points Static (Steady-State) Object Number: 1 Change Event Object Number: 2 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 1 (Binary Input with status) Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time) Point Name Description...
  • Page 26 Point lists Binary Input Points Static (Steady-State) Object Number: 1 Change Event Object Number: 2 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 1 (Binary Input with status) Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time) Point Name Description...
  • Page 27 Binary Input Points Binary Input Points Static (Steady-State) Object Number: 1 Change Event Object Number: 2 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 1 (Binary Input with status) Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time) Point Name Description...
  • Page 28 Point lists Binary Input Points Static (Steady-State) Object Number: 1 Change Event Object Number: 2 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 1 (Binary Input with status) Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time) Point Name Description...
  • Page 29 Binary Input Points Binary Input Points Static (Steady-State) Object Number: 1 Change Event Object Number: 2 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 1 (Binary Input with status) Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time) Point Name Description...
  • Page 30 Point lists Binary Input Points Static (Steady-State) Object Number: 1 Change Event Object Number: 2 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 1 (Binary Input with status) Change Event Variation reported when variation 0 requested: 2 (Binary Input Change with Time) Point Name Description...
  • Page 31 Control Relay Output Blocks/Binary Output Status Control Relay Output Blocks/Binary Output Status Binary Output Status Points Object Number: 10 Request Function Codes supported: 1 (Read) Default Variation reported when variation 0 requested: 2 (Binary Output Status) Control Relay Output Blocks/Binary Output Status Object Number: 12 Request Function Codes supported: 3 (select), 4 (operate), 5 (direct operate), 6 (direct operate, no ack) Point In-...
  • Page 32 Point lists Binary Output Status Points Object Number: 10 Request Function Codes supported: 1 (Read) Default Variation reported when variation 0 requested: 2 (Binary Output Status) Control Relay Output Blocks/Binary Output Status Object Number: 12 Request Function Codes supported: 3 (select), 4 (operate), 5 (direct operate), 6 (direct operate, no ack) Point In- Name Description...
  • Page 33 Control Relay Output Blocks/Binary Output Status Binary Output Status Points Object Number: 10 Request Function Codes supported: 1 (Read) Default Variation reported when variation 0 requested: 2 (Binary Output Status) Control Relay Output Blocks/Binary Output Status Object Number: 12 Request Function Codes supported: 3 (select), 4 (operate), 5 (direct operate), 6 (direct operate, no ack) Point In- Name Description...
  • Page 34 Point lists Counters Counters Static (Steady-State) Object Number: 20 Change Event Object Number: 22 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 1 (32-Bit Counter with Flag) Change Event Variation reported when variation 0 requested: 1 (32-Bit Counter without Time) Point In- Name Description...
  • Page 35 Analog Inputs Analog Inputs Analog Inputs Static (Steady-State) Object Number: 30 Change Event Object Number: 32 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 02 (16-Bit Analog Input) Change Event Variation reported when variation 0 requested:02 (Analog Change Event without Time) Point In- Name Description...
  • Page 36 Point lists Analog Inputs Static (Steady-State) Object Number: 30 Change Event Object Number: 32 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 02 (16-Bit Analog Input) Change Event Variation reported when variation 0 requested:02 (Analog Change Event without Time) Point In- Name Description...
  • Page 37 Analog Inputs Analog Inputs Static (Steady-State) Object Number: 30 Change Event Object Number: 32 Request Function Codes supported: 1 (read) Static Variation reported when variation 0 requested: 02 (16-Bit Analog Input) Change Event Variation reported when variation 0 requested:02 (Analog Change Event without Time) Point In- Name Description...
  • Page 38 Point lists SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2...
  • Page 39 Glossary Asynchronous interface module with (electrical) isolated RS485 interface for the SIPROTEC devices from Siemens. Asynchronous interface module with optical interface for the SIPROTEC devices from Siemens. Automatic Recloser Continuous Function Chart Double Command Parameterization system for SIPROTEC devices DIGSI...
  • Page 40 SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2...
  • Page 41 Index Index ..........4 ..........5 Additional support Note (definition) ........10 Alarm summary event .......... 12 Analog Inputs ........4 Applicability of manual ..........6 Parameter names ..........6 Parameter options ...........11 Pulse output ........10 ............11 Binary Input Points pulse output ....11 Binary Outputs / Commands ......5 Qualified personnel (definition) ...........5...
  • Page 42 Index SIPROTEC DNP 3.0 - Bus mapping / Point lists 7SJ80/7SK80/7RW80 C53000-L2040-A320-2...

This manual is also suitable for:

Siprotec 7sk80Siprotec 7rw80

Table of Contents